Certification: CE / ISO / Explosion-proof
Place of Origin: China
MOQ: 1
Price: Negotiable
Payment Terms: L/C, D/A, T/T, Western Union, MoneyGram
Supply Ability: 1000pcs
Delivery Time: 5~8 working days
Packaging Details: Carton / Wooden Box
DN(mm): DN15~DN300
Pressure: 1.6MPa
Connection: DN15~DN40 Threaded / DN50~DN300 Flange connection
Communication: RS-485 / MBUS / Lora433MHZor 868MHZ / GPRS
Accuracy: Class 2
Protection: IP67 / IP68
Installation: Default is Inflow, for return flow need to indicate when ordering
Power supply: High Power Lithium battery
Temp. sensor: 1.5m standard a pair of PT1000 Temperature Senso
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
  • Submit Buying Request
    • Product Details
    • Company Profile

    Wirless BTU Ultrasonic Water Meter High Accuray For Apartments / Buildings

    Wirless Ultrasonic Btu Meter Lora / GPRS Ultrasonic Heat Meter For Residence / Apartments / Buildings


    Features


    ☆ Measure Heat.
    ☆ Show supply/return water temperature and differential temperature.
    ☆ Display pile flow measure and instantaneous flow measure.
    ☆ Running time display.
    ☆ Cool measure and display (for heat/cold Ultrasonic Heat Meter )


    Description


    KACISE KUHM2100 series heat meters adopt most advanced non-magnetic technology and it features elegant appearance, accurate measurement, convenient management, steady operation, strong anti-erosion, and long using life, which is secure and economic.
    It is widely used in the heat system with concentrated heat supplying management, separate household data collecting management.
    Varies of communication modes are optional according to the users’ need..


    Installation and Attentions

    The heat meter both can be installed in Inflow pipe or Return flow pipe (factory default installed in the inflow pipe, if need to install on the return pipe, must be clearly indication before the factory during the production). When installation, should pay attention to the flow direction of medium is as the same as the arrow on the heat meter pipe body.

    Special note: no matter the heat meter installed on inflow pipe or return flow pipe, the temperature sensor should be properly connected ( red label for inflow pipe, blue label for return pipe)


    Specifications


    Nominal DiameterDN15DN20DN25DN32DN40
    Dimension (Length mm)110130160180200
    Max flow (m3/h)3571220
    Norm flow(m3/h)1.52.53.5610
    Min flow(m3/h)0.030.050.070.120.2
    Max flow reading999999.99(m3)
    Max heat reading99999999(KW·h)
    Power supply3.6VDC
    Battery life>6 years ( Lithium battery)
    Accuracy classClass 2
    Communication modeInfrared interface , M-BUS/RS485
    Press loss≤ 0.025 Mpa ( under normal flow)
    IP classIP 68
    Temperature range(4--95) °C
    Temperature difference range(3--70) k
    Starting temperature difference0.01k
    Temperature sensorPt 1000
    Ambient temperature+5°C -- +55°C
    Ambient levelLevel A
    InstallationHorizontal/ vertical installation
    Monitor8 digits
    Length of temperature sensor1.5m
    Working current45uA
    Data storageStore historical data up to last 24 months

    Instrument Common Problem


    The meter cannot work normally

    Heating system is working or not;

    Globe valve is opened entirely or not;

    the pipe is blocked or not;

    the lead seal is complete or not;

    Battery is good or not;

    heat meter isn’t counting

    ①, heat meter reversed installation

    ②, transducer cables are broken

    ③, the filter is be blocked on heat supply pipe of in the resident room

    How to determine the filter whether block?

    Inflow temp. is normal, return flow temp. is too low, the temp. difference of inflow and return flow is more than 10°, flow rate is too low(m3/h), or now flow rate, usually the filter is blockage, or user does not use.

    Solution:Close the valve (inflow and return flow valve), remove the filter, to observe whether filter is black, clean filter and inside of it, then install the filter, open pipe valves, wait 3 mins to check whether the flow rate and temp. is normal.

    Heat meter data abnormal or jumping

    ①, Installation position is not correct, down water level

    ②, Front and back straight pipes are too short, bend is too big, front pipe diameter is

    changing bigger.

    Heat meter has flow quantity, no heat, or heat is very big

    ①, Without heat is usually reversed installation of inflow and return flow temp. sensors

    ②, Heat is very big, because the temp. sensor measure temp. incorrectly, temp. difference is very big.

    Heat meter abnormal temp., or the temp. is 0

    ①, the temp. sensor cable is broken

    ②, Temp. sensor stainless steel casing is broken.


    Technical Specification


    DiameterMin FlowQuantity of FlowMax FlowLength
    qmin(m³/h)qp(m³/h)qmax(m³/h)mm
    DN150.031.53110
    DN200.052.55130
    DN250.073.57160
    DN320.12612180
    DN400.21020200
    Measurement AccuracyCJ128-2007<Heat Meter>Class 2
    ConnectionDN15~DN40 Threaded connection/DN50~DN300 Flange connection
    Pressure Loss≤0.02MPa
    Maximum Working Pressure(MWP)1.6MPa
    Flow Measuring Range1:100
    Temperature Sensor1.5m standard a pair of PT1000 Temperature Sensor (cable length could be changed)
    Data StorageContinuous store of 18 months record
    Power-off ProtectionAfter power-off, meter could save all the record of before flow rate and the corresponding time, after power back, it recovery measure function automatically, and ensure the time continuation
    Remote TransmissionMBUS/RS-485
    Power SupplyHigh Power Lithium battery
    Protection ClassIP67 (IP68 need to modified)
    Environmental ClassClass B
    Temperature Range(5~95)℃
    Temperature Difference(3~90)K
    Installation WayInflow or Return flow(Default is Inflow, for return flow need to indicate when ordering)
    Installation PositionHorizontal / Vertical
    PermanenceService cycle≥6 years
    Display8-bit LCD display
    Anti-magnetic DisturbanceWhen the intensity of magnetic field interference is not more than 100 ka/m, should not affect water meter measurement and remote transmission characteristics

    Quality Wirless BTU Ultrasonic Water Meter High Accuray For Apartments / Buildings for sale
    Send your message to this supplier
     
    *From:
    *To: Xi'an Kacise Optronics Co.,Ltd.
    *Subject:
    *Message:
    Characters Remaining: (0/3000)
     
    Inquiry Cart 0

    Friendly Links: www.everychina.com

    Home| Products| Suppliers| Quality Suppliers| Site Map |About Us |Contact Us |Help |关于我们 |联系我们

    Copyright © 2009 - 2024 bjjsgy.com. All rights reserved.