Product characteristics
| Electrical design |
PNP/NPN; (configurable) |
| Communication interface |
IO-Link |
| Dimensions [mm] |
250 x 28 x 16.7 |
Application
| Application |
Continuous level measurement behind non-metallic and non-conductive surfaces |
| Media |
dry bulk material; aqueous solutions; oils |
| Cannot be used for |
very adhesive media |
Electrical data
| Operating voltage [V] |
10...30 DC; (IO-Link: 18...30 DC) |
| Current consumption [mA] |
< 50 |
| Protection class |
III |
| Reverse polarity protection |
yes |
| Max. power-on delay time [ms] |
1300 |
| Measuring principle |
capacitive |
Inputs / outputs
| Number of inputs and outputs |
Number of digital outputs: 3 |
Outputs
| Electrical design |
PNP/NPN; (configurable) |
| Number of digital outputs |
3 |
| Permanent current rating of switching output DC [mA] |
200 |
| Max. resistance switching output [Ω] |
8 |
| Short-circuit protection |
yes |
| Type of short-circuit protection |
yes (non-latching) |
| Overload protection |
yes |
Monitoring range
| Measuring range [mm] |
< 200 |
Measuring/setting range
| Detection range [mm] |
228 |
| Set point SP [%] |
5...95 |
| Reset point rP [%] |
4...94 |
| In steps of [%] |
1 |
Accuracy / deviations
| Repeatability [% of the final value] |
2 |
| Offset deviation [% of the final value] |
4 |
| Resolution [% of the final value] |
1 |
| Linearity deviation [% of the final value] |
1 |
Software / programming
| Parameter setting options |
Damping; hysteresis / window; fault indication; Diagnostic function; Sensitivity; internal temperature; limitation of measuring range; adjustable switching delay; zero-point calibration; direction of installation; LEDs can be deactivated |
Interfaces
| Communication interface |
IO-Link |
| Transmission type |
COM2 (38,4 kBaud) |
| IO-Link revision |
1.1 |
| SDCI standard |
IEC 61131-9 |
| Profiles |
Digital Measuring Sensor Profile, Common Profile |
| SIO mode |
yes |
| Required master port class |
A |
| Process data analog |
1 |
| Process data binary |
3 |
| Min. process cycle time [ms] |
9.6 |
| IO-Link process data (cyclical) |
| Function |
bit length |
| process value |
16 |
| exponent |
8 |
| device status |
4 |
| binary switching information |
3 |
|
| IO-Link functions (acyclical) |
direction of installation; limitation of sensor elements; Sensitivity; minimum recognition threshold; Performance in case of a fault; error delay; Damping; LED mode; switch-on cycle counter; operating hours counter; switching cycles counter; min./max. process value; internal temperature; min./max. internal temperature; diagnostic data level |
| Supported DeviceIDs |
| Type of operation |
DeviceID |
| default |
924 |
|
| Note |
| For further information please see the IODD PDF file at "Downloads" |
|
Operating conditions
| Applications |
DIN EN 60654-1 application class B2 |
| Ambient temperature [°C] |
-20...80 |
| Storage temperature [°C] |
-25...85 |
| Protection |
IP 65 |
Tests / approvals
| EMC |
| DIN EN 61000-6-4 30 - 230 MHz |
40 dBµV/m QP / 10 m distance |
| 230 - 1 GHz |
47 dBµV/m QP / 10 m distance |
| DIN EN 61000-4-2 |
± 25 kV AD / ± 25 kV CD |
| DIN EN 61000-4-3 |
80 MHz - / 1 GHz 10 V/m |
| DIN EN 61000-4-4 |
± 2.5 kV / 5 kHz |
| |
± 2.5 kV / 100 kHz |
| DIN EN 61000-4-6 |
10 V |
|
| Shock resistance |
|
| Vibration resistance |
| EN 60068-2-6 |
5 g (10...2000 Hz) |
|
| MTTF [years] |
290.43 |
| UL approval |
| Ta |
-25...60 °C |
| Enclosure type |
Type 1 |
| voltage supply |
Limited Voltage/Current |
| UL approval number |
D006 |
| File number UL |
E174191 |
|
Mechanical data
| Weight [g] |
377.5 |
| Dimensions [mm] |
250 x 28 x 16.7 |
| Material |
PBT; PC; |
Displays / operating elements
| Display |
| Power |
1 x LED, green |
| Switching status |
3 x LED, yellow |
| Function |
20 x LED, green |
|
Accessories
| Items supplied |
| adhesive tape: 1 x 23 mm x 240 mm |
|
| Accessories (optional) |
| Mounting adapter: 2, E12675 |
| Mounting adapter: 2, E12676 |
| Fixing strap: 5, E10880 |
| adhesive tape: 10, E12677 |
|
Remarks
| Remarks |
| When used on IO-Link class B masters, switching outputs OUT2, OUT3 must be turned off |
|
| Pack quantity |
1 pcs. |
Electrical connection
| Connection |
Connector: 1 x M12; coding: A |
Electrical connection - plug