| Sign In | Join Free | My bjjsgy.com |
|
| Categories | Transformer Test Equipment |
|---|---|
| Brand Name: | HNMC |
| Model Number: | MCTL-100 |
| Place of Origin: | China |
| MOQ: | 1 pc |
| Price: | Negotiable |
| Supply Ability: | 200 per month |
| Delivery Time: | 20-25 Days |
| Packaging Details: | Carton package |
| Voltage measure range: | 0-750V |
| Current measure range: | 0-100A |
| Accuracy: | 0.2% |
| Power supply: | 85-265V |
| Display: | LCD |
| Weight: | 4KGS |
| Communication port: | USB, RS232 |
| Application: | worksite, lab |
Portable Transformer Test Equipment-Transformer Loss Test Set MCTL-100
Technical Index
| Item | Technical Index | ||
| Voltage measure range | 0~750V | ||
| Current measure range | 0~100A,auto ranging | ||
Accuracy | Voltage ,Current ,Frequency | ±0.2% | |
| Power | ±0.5%(CosΦ>0.1), ±1.0%(0.02<CosΦ<0.1) | ||
| Operating temperature | -10℃~ +40℃ | ||
| Power supply | AC85V~265V | ||
Insulation | Insulation resistance between voltage/current input terminal and housing: | ≥100MΩ | |
| Power Frequency Withstand voltage between power supply input and housing | 2KV (effective value), one minute | ||
| Dimension | 35cm×26cm×13cm | ||
| Weight | 4kg | ||
|