Dwyer MS-111 Micro Differential Pressure Transmitter 4-20mA Output 50 Pa Accuracy for HVAC Monitoring

Price Negotiable
Price: usd76 piece/pieces
MOQ: 1
Delivery Time: 5-8 work days
Brand: Dwyer
Product Description
MS-111 Micro Differential Pressure Transmitter Overview

The Dwyer MS-111 is a versatile micro differential pressure transmitter designed for monitoring pressure and wind speed in various industrial applications. This compact instrument features field-selectable units, adjustable output signals, and advanced magnetic sensing technology for superior long-term performance.

Key Applications
  • Building pressure monitoring systems
  • Duct pressure monitoring in HVAC systems
  • Fan velocity measurement and control
  • Zone differential pressure monitoring
  • Filter condition monitoring and maintenance
Product Features
  • Field-selectable English or Metric measurement ranges
  • Field-upgradeable 4-digit LCD display
  • Adjustable output signal damping with optional display
  • Square root output capability for pitot tubes and flow sensors
  • Magnetic sensing technology for reliable long-term performance
Technical Specifications
Parameter Specification
Model MS-111
Output Signal 4~20 mA
Display 4-digit LCD
Service Medium Air and non-combustible compatible gases
Accuracy ±1% for 0.25" (50 Pa)
Stability ±1% FS/year
Temperature Range 0 to 150°F (-18 to 66°C)
Pressure Limits 1 psi maximum operation; 10 psi burst
Power Requirements 10 to 35 VDC (2-wire); 17 to 36 VDC or isolated 21.6 to 33 VAC (3-wire)
Response Time 300 ms
Mounting Orientation Diaphragm in vertical position
Weight 230g
Product Images
MS-111 Differential Pressure Transmitter front view showing LCD display and housing
MS-111 Transmitter side view and mounting details
MS-111 Differential Pressure Transmitter wiring diagram and connections
MS-111 Transmitter installation example in industrial setting
Installation Notes

Important Safety Instructions:

  • Cables must be fitted through 1/2" NPT cable gland or ATEX/IECEx conduit (not supplied)
  • Ensure tight closure of cover and cable gland to maintain IP66 rating
  • Open cover only after de-energizing the instrument
  • Always check local safety rules and warnings on unit and manual for correct use in hazardous areas