20hp Portable Air Cooled Water Chiller Modular
20HP Laser Cutting Machine Air Cooled Chiller For Laser Plate Cutting Machine
Laser chiller is used for laser cutting, laser welding, laser engraving, etc.
The composition of laser chiller is composed of compressor, condenser, throttling device, evaporator, water tank and water pump and other accessories.
Laser Chiller Specification
|
Model Item |
AL-20W(D) | |
| Nominal cooling capacity | Kcal/h | 51772 |
| kw | 60.2 | |
| Input power | kw | 20.76 |
| Power supply | 3PH~380V/50HZ | |
| Refrigerant | Type | R22 |
| Type of control | Expansion valve | |
| Compressor | Type | Hermetic scroll type |
| Power (kw) | 16.2 | |
| Condenser | Type |
Finned copper tube+low noise outer rotor fan |
| Power(kw) | 1.56 | |
| Cooling air flow | 20000 | |
| Evaporator | Type | Water tank with coil |
| Chilled water flow | 10.38 | |
| Tank volume(L) | 350 | |
| Inlet/outlet pipe chiller(inch) | 2 | |
| Water pump | Power(KW) | 3 |
| Lift(m) | 28 | |
| Safety protection | compressor over temperature, over-current protection, high and low pressure protection, over -temperature protection ,flow switch protection,phase sequence or missing phase protection,exhaust overheating protection | |
| Net weight | kg | 835 |
| Dimension | mm | 2000*1130*1820 |
Laser cutting machine water chiller failure possible causes:
The inlet end of the pipeline is blocked and air is inhaled;
Reverse connection of import and export pipeline;
Pump motor reversal or motor and pump shaft wear;
The oil used does not conform to the specifications or the level of the oil tank is lower than the lower limit;
The oil-water filter is blocked or the oil-water floating pressure ball is faulty;
Laser cutting machine water chiller fault solution:
Check and clean the oil circuit and tighten the pipeline;
Check that the import and export directions are correctly connected;
Updating the pump motor; Switch the red and white lines under the cumulative thermoelectric relay (51P);
As described in the instruction manual, select the compound oil and check whether the liquid level of the oil tank is normal;
Try to replace or clean the filter and try to replace the pressure float detection switch.
Featurers for air cooled laser chiller
- the host selected original authentic machine, built-in safety protection, low noise, power saving and durable.
- all stainless steel pump, high head, especially suitable for conveying high water quality requirements of the industry.
- the electrical parts are original authentic to ensure stable machine work, long life.
- super (high, low) and mild flow dual protection, equipped with flow protection switch, when the pump failure or water is too little, flow switch operation, automatically disconnect the laser power supply, to prevent the laser head water shortage overheating, or even rupture.
- 304 stainless steel evaporator, to prevent pure water in the transport process to produce solid and other metal impurities.
Get in Touch