ICT-Based No-Disconnect Three-Phase Meter Test Equipment

Price Negotiable
Price: negotiation
MOQ: 1 Piece
Delivery Time: 30 days after order confirmed
Brand: GENY
Product Description
ICT-Based No-Disconnect Three-Phase Meter Test Equipment

For three-phase energy meters with inseparable current and voltage circuits, our system integrates a high-accuracy 1:1 electronic compensation ICT at each meter position, enabling true no-disconnect calibration without external isolation transformers. This solution supports testing under actual wiring conditions, delivers more realistic error characteristics, improves calibration efficiency, and fully meets ICT-related technical requirements for utilities, laboratories, and manufacturers.

Key Features
  • ICT installation in each meter position for testing three-phase meters with closed links between current and voltage measuring circuits (I-P links)
  • Capable of measuring mechanical and electronic meters through automatic, semi-automatic, or manual operation
  • Supports testing of 3P4W, 3P3W, and 1P2W meter configurations
  • Comprehensive testing modes including active power, reactive power, and cross-connected reactive power
  • Simultaneous measurement of meters with same specifications but different meter constants for accuracy
  • Automatic positioning rotor mark of mechanical meter disc for improved efficiency
  • Initiating test and creep test capabilities
  • Comprehensive safety features including overload, short-voltage, and open-current circuit protection
  • Synchronized movement of scanning heads for streamlined control process
  • Lightweight, durable aluminum alloy construction with corrosion resistance
  • Windows-compatible testing software (2000, XP, 7, 8, 10) with modules for real-time error, harmonic, demand, and influence testing
Technical Specifications
Technical Specification YC1893D-ICT-6
Number of meter positions equipped ICT 6
Accuracy class of ICT 0.05 / 0.01
Accuracy 0.05
Power Source YCS-103-250
Standard Meter SZ03A-K6 / SZ03A-K8 (customized)
Scanning Head YCG-S Series
Voltage Specifications
Test voltage output (Phase-Neutral) 3x(24V~288V)(or customized)
Power of the voltage output Max. 3x100VA
Resolution Better than 0.01% of full scale value of range
Setting accuracy Better than 0.05% at the final range value
Stability Better than 0.005% /h (integration time 150s)
Load regulation from 0~max. load Better than 0.01%
Distortion factor Better than 0.3% for linear resistance load
Harmonic 2nd~21st free programmable
Current Specifications
Test current output 3x(1mA~100A)
Power of the current output Max. 3x150VA
Resolution Better than 0.01% of full scale value of range
Setting accuracy Better than 0.05% at the final range value
Stability Better than 0.005% /h (integration time 150s)
Load regulation from 0~max. load Better than 0.01%
Distortion factor Better than 0.3% for linear resistance load
Harmonic 2nd~21st free programmable
Phase Angle & Frequency
Phase Angle Range 0~360%
Phase Angle Resolution 0.01%
Phase Angle Setting Accuracy 0.10%
Frequency Range 45Hz~65Hz
Frequency Resolution 0.01Hz
Error Display
Type of error display Red LED
Resolution of error displays 8 digitals
ICT-Based No-Disconnect Three-Phase Meter Test Equipment - Professional calibration system for energy meters

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Guangzhou GENY Electric Co., Ltd
Location ROOM 107, 1ST FLOOR, No. 602 GUANGSHAN ER ROAD, TIANHE DISTRICT, GUANGZHOU, CHINA POSTCODE: 510663
Contact Person John Shen

Request A Quote

Please check your email address.
Your message must be at least 20 characters.