35kV Cable Fault Location System with 2048J Discharge Power
| Attribute | Value |
|---|---|
| Product name | Cable fault location set |
| Impulse voltage | 0-35kV |
| High pressure partial pressure | 2.5 |
| Discharge power | 2048 J |
| Impact power | 2000W |
| Power | Electronic |
The XHHV535-4TSB cable fault location system is designed to detect main insulation faults in power cables with voltage levels up to 35kV and calibrate cable length. This comprehensive system includes a cable fault tester and high-voltage pulse generator.
The cable fault tester features an intuitive software interface with touch operation, centralized microcontroller control, and a built-in high-capacity lithium-ion battery. Its independent power supply system prevents interference during impact discharge, ensuring stable and reliable operation.
This system is suitable for detecting various faults in power cables, including low-resistance, short-circuit, open-circuit, broken wire, high-resistance leakage, and high-resistance flashover faults across different cable types and materials.
| Surge HV voltage | 0-8kV/16kV/32kV |
| High voltage side current | 0-60mA |
| Internal capacitor | 4μF/32kV, 16μF/16kV, 64μF/8kV |
| Surge time | Auto surge ~4s, manual control available |
| Surge energy | 2048J |
| Surge power | 2KVA |
| Weight | ≤120kg |
| Power supply | AC220V±15%, 50Hz±2Hz |
| Operating temperature | -20℃ to +50℃ |
- Sampling frequency: 1MHz-400MHz
- Low voltage pulse amplitude: 300V±15%
- Distance measurement range: ≥120km
- Test ranges: 100m/300m/500m/1km/3km/5km/10km/25km/50km/100km
- Pulse width: 0.15μS to 10μS
- Minimum resolution: 0.07m
- Test blind area: ≤10m
- Measurement error: ≤±(0.5%×L+1m), where L is cable length
- Power supply: Built-in 10.4AH lithium battery (5 hours operation, 2 hours charge time)
The XHDD503E pinpointer uses acoustic-magnetic synchronization technology to precisely locate cable faults. When combined with a high-voltage pulse generator, it detects flash discharge phenomena through vibration waves, sound waves, and electromagnetic waves, displaying fault distance and producing audible signals for precise fault localization.
- Sound channel bandwidth: 100Hz-1600Hz (all-pass, low-pass, high-pass, band-pass options)
- 8-level adjustment for sound, magnetic, and voltage channels
- Sound output: 16-level gain (0-112dB), 350Ω impedance
- Detection range: 0.00-99.99ms, 75mV-75V
- Detection accuracy: ≤0.1m (positioning), ≤0.5m (step voltage/path)
- Power supply: 4×18650 lithium batteries (8+ hours standby)
- Operating temperature: -25℃ to 65℃
- Dimensions: 428×350×230mm
- Weight: 7kg
Get in Touch