XHJK531Overhead line fault tester

Our overhead line and cable fault detector is designed for efficient identification and location of faults in overhead power lines and cables. This essential tool helps maintenance teams quickly pinpoint issues to minimize downtime and improve system reliability.
Technical specification
Positioning accuracy 0.2 meters
Transmitter output characteristics

(1)Output frequency 1Hz

(2) Open circuit voltage: fundamental wave effective value 0~2800V,

(Pulsating DC, peak value 8kV, equivalent to the peak phase voltage of a 10kV line);

(3) Short circuit current: fundamental wave effective value 0~35mA (pulsating DC, peak value 100mA)

The wireless communication distance between the sensor and the receiver  not less than 100m
Transmitter power maximum power 900W

1). Power supply: Turn on the power switch, the power indicator light is on, but there is no signal output from the transmitter at this time.

2). Start output:

 First, adjust the "Output Adjustment" knob to the zero position. The "Zero Position Indicator" light turns on. Then press the "High Pressure Close" button and slowly adjust the "Output Adjustment" knob clockwise. The "Zero Position Indicator" light goes out and the transmitter starts to output. , continue to adjust the "Output Adjustment" knob to maximize the input current, and the protection indicator light does not light up. If the protection indicator light lights up, it means that the line fault resistance is small and the input current is too large. At this time, you need to adjust the "Output Adjustment" knob counterclockwise to the zero position, and then readjust it to the appropriate position.

3). Stop output: If you need to stop output, press the "High Voltage Point" button.

4). After the work is completed, turn off the power and remove the wiring.

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Xi'an Xu&Hui Electromechanical Technology Co., Ltd.
Location Building B8-01, Phase I, Ronghao Industrial City, No. 2098, Weiyang 9th Road, Gaoling District, Xi'an, China
Contact Person Serena

Request A Quote

Please check your email address.
Your message must be at least 20 characters.