Shenzhen HRD SCI&TECH CO.,Ltd
                                                                                                           
Verified Supplier
16 Years
Since 2010
Menu

SCR Ac Dc Rectifier Industrial 2.4kw To 220kw Capacity

Price Negotiable
Price: 5000USD
MOQ: 1
Delivery Time: 5-6weeks after deposit
Brand: HRD/OEM
Product Description

R6000 Series Industrial Charger & DC UPS, With Input Isolation Transformer, output 24/48/ 110/125/220VDC,50A-2000A.

Introduction:R6000 series is a top-tier industrial charger&DC UPS is desiged with  thyristors  with DSP control for industrial .Its super reliability ensures  providing  high reliability powersupply  for DC loads which recharging  batteries;

It can also be used as independent DC power supply without battery.

 

 

Perfect Applications:
P e t r o l e u m , petrochemical, power plant, natural gas, electric power, marine, heavy industry, mining, transportation and other industries .
 

Features and benefits:

1) SCR rectifier with DSP control technology, overvoltage,undervoltage protection for reliable operation in all mains conditions

2)Input isolation transformer for AC- DC

3)High operating safety and reliability, even under difficultcircumstances over long periods of time
 

4) Adjustable manual and automatic charging mode for maximum flexibility on operation
 

5)Digital control panel and touch screen for meters, alarms,and history events for maximum flexibility on monitoring

6)Parallel operation for redundancy requirements

7) Support all charging mode for vented/sealed lead acid batteries and Ni- Cd batteries
8)More than 12,000 history records to position issues quickly and accurately
9) Front accessibility for easy maintenance

10)Battery charging temperature compensation
11) Cable voltage drop compensation
Technical specificaions:

Technicaldata:

 

Input

Rated voltage 230Vac 1phase or 400Vac 3phase
Voltage range 220/230Vac -15%~+20%
or380/ 400Vac -15%~+20%
Frequency range 45-66Hz


 

Output

Rated voltage 24,48,60,110,125,220Vdc
Operating Voltage

Floating:75%-125% of rated voltage at full load and rated voltage+/-10%

Equalizing:75%-125% of rated voltage at full load and rated supply voltage(0-10%)

Commissioning:75%-140% of rated voltage at half load and rated supply voltage(0-10%)

Static voltage regulation +/-0.5%
Ripple Voltage ≤1%
Charging characteristic IU( according to DIN41773)
System and Environmental Protection degree IP21(Optional to IP43)
Cable entry bottom
access front
Color RAL7035
Operation temperature 0-40 centigrade
Storage temperature -25-70centigrade
Noise <65dBA
Altitude <1000m(derating according to EN62040-3)
Cooling Forced Ventilation

 

Standard

Safe IEC60146
EMC IEC61000-6-2 IEC61000-6-4
Performance IEC601146
Communication RS-232/485,Modbus Protocal







 

 

Rating

Rated Voltage(Vdc) 24 48/60 110/125 220







 

Rated Current(A)

25 25 25 25
50 50 50 50
75 75 75 75
100 100 100 100
150 150 150 150
200 200 200 200
300 300 300 300
400 400 400 400
500 500 500 500
600 600 600 600
800 800 800 800
1000 1000 1000 1000
2000 2000 2000 2000
3000 3000 3000 /
4000 4000 4000 /

Note: Customized type is acceptable.



 
 

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Shenzhen HRD SCI&TECH CO.,Ltd
Location 1st floor, 56A building, Bao’tian Industrial Park,Xixiang Town Bao’an District, Shenzhen City
Contact Person Hunter Chen

Request A Quote

Please check your email address.
Your message must be at least 20 characters.