QBJ-3WZ Speed Monitoring Emergency Trip Protection Device
The QBJ-3WZ emergency shutdown protection device serves as a critical safety component for steam turbine units, providing comprehensive monitoring throughout operation. During normal conditions, it continuously monitors turbine speed. In overspeed scenarios, the secondary emergency shutdown striker activates via centrifugal force, initiating an immediate turbine shutdown. The system employs three QBJ-CS-1 type sensors: one for speed measurement and two dedicated to emergency shutdown functions.
Technical Specifications
| Speed Measurement Range | 300~9999 rpm |
| Speed Display Range | 0~9999 rpm |
| Speed Measurement Accuracy | 0.1% |
| Input Signal | Vp-p=0.05~30V |
| Emergency Interruption Impactor Detection Speed | n>2500 rpm |
| Emergency Interruption Detection Speed Accuracy | n<±5 rpm |
| Overspeed 1 Alarm Speed | 3300 rpm (user-configurable) |
| Overspeed 2 Alarm Speed | 3240 rpm (user-configurable) |
| Alarm Node Output Capacity | AC220V (3A) |
| Power Supply | AC220V±10%/50Hz |
| Sampling Frequency | 1/64 second incremental sampling |
| Instrument Installation | Panel mounting, Mounting Hole Dimensions: 154mm * 78mm * 260mm (W*H*D) |
| Operating Environment - Instrument | -25℃~45℃ (Relative Humidity ≤80%) |
| Operating Environment - Sensor | -10℃~100℃ (Relative Humidity ≤90%) |
| Sensor Mounting Thread | M16*1 |
| Sensor Screw Length | L60~200mm (customizable) |
Primary Functions
- Real-time display of current unit speed with emergency trip indication after striker deployment
- Emergency stop functionality for immediate shutdown
- Overspeed alarm system with configurable thresholds
- Maximum turbine speed capture and recording
- Block display function for operational status
- Enhanced anti-interference capability for reliable operation
This protection device ensures operational safety and reliability for steam turbine systems through precise speed monitoring and rapid emergency response capabilities.