Automatic Voltage Regulation 1200kW Natural Gas Generators Electric Governor 3 Phase 4 Wire
Automatic Voltage Regulation 1200kW Natural Gas Generators Electric Governor 3 Phase 4 Wire
1. Description of 1200kW Natural Gas Generating Set:
1200kW natural gas generating sets(1200GF-T1) are powered by model H16V190ZLT-2 gas engine produced by our company. Complying with National Standard “GB2820 General Specification for Industrial Frequency Diesel Generating Sets(eqv ISO 8528)” and with reference to “IEC60034-I” rotary generator standard, the sets are equipped with high quality alternator of both home & abroad and self-made control panel according to customers requirement.
LE16V190ZLT-2 natural gas engine is adopted advanced governor of American WOODWARD Company. It is the engine that mixes air and fuel before turbocharger. The power performance, fuel economy and reliability of the gas engine reach world advanced level by adopting world advanced outer mixing mode, electronic control technology and lean-burnt strategy.
This 1200Kw gensets have the features of accurate voltage regulating, good dynamic performance, less voltage waveform distortion, high efficiency, compact structure, easy to maintain, low speed, reliable and long life operation and cost-effective.
The 1200Kw gensets can either transfer electricity directly to load or be combined in a power station with two or more than two sets. They can be used as normal and stand-by power in oil field, factory, resource development base, etc
2. Main Specification of Genset:
|
Model of genset |
LF1200GF-T1 |
|
Model of engine |
LE16V190ZLT-2 |
|
Model of alternator |
1FC6 564-6LA42(SIEMENS technology) |
|
Coupling method |
Elastic coupling |
|
Rated speed(r/min) |
1000 |
|
Rated power(kW/kVA) |
1200/1500 |
|
Rated voltage(V) |
400 |
|
Rated frequency(Hz) |
50 |
|
Rated power factor |
0.8 lagging |
|
Voltage regulation |
Automatic |
|
Supply connecting |
3 phase 4 wire |
|
Governor |
Electric governor |
|
Control model |
Remote electric control, Hand control |
|
Starting method |
24V DC electric starting motor |
|
Cooling method |
Water cooling system with horizontal radiator |
|
Overall dimension L×B×H(mm) |
6410×2335×2740 |
|
Net weight(kg) |
19000 |
3. Main Electrical Performance Data:
|
Voltage |
Frequency |
||||||
|
Stable regulating rate |
Instantaneous regulating rate |
Recovery time |
Fluctuation |
Stable regulating rate |
Instantaneous regulating rate |
Recovery time |
Fluctuation |
|
±2.5% |
+20%-15% |
1.5s |
0.5% |
5% |
±10% |
7s |
0.5% |
|
Voltage adjustment range: idle load voltage adjusted 95~105% rated voltage. |
|||||||
4. Control Panel
The DSE7510 is an Automatic Engine Control Module, designed to provide advanced load share functionality for diesel and gas generating sets that include electronic and non-electronic engines.
The module’s load share functions
include automatic synchronising with built-in synchroscope and closing onto dead bus. Direct and flexible outputs from the module are provided to allow connection to the most commonly used speed governors and automatic voltage regulators (AVRs).
5. Main Specification of Engine
Note: Rated power is the effective power of engine at rated speed under standard environment conditions, according to the standard of GB/T 6072 (idt ISO 3046). The standard environment conditions are: atmospheric pressure: 100kPa, relative humidity: 30%, ambient temperature: 25 degrees Celsius, low heat value of gas: 36MJ/Nm3, max. load,. Otherwise, the engine power shall be corrected through conversion. MN≥80.
|
Model of engine |
LE16V190ZLT-2 |
|
Rated Speed(r/min) |
1000 |
|
No. and layout of cylinders |
16-cylinder,60°Vee |
|
Type |
Four stroke, water cooled, turbocharged and after-cooled, spark plug |
|
Type of combustion |
Lean burn |
|
Gas pressure(bar) |
1~4 |
|
Specific heat consumption (kJ/kW.h) |
≤9500 |
|
Specific oil consumption (g/kW.h) |
≤1.0 |
|
Bore(mm) |
190 |
|
Stroke (mm) |
215 |
|
Compression ratio |
10:1 |
|
Total displacement (L) |
97.53 |
|
Direction of rotation |
Counter-clockwise(facing to flywheel) |
|
Lubrication method |
Pressure and splash lubrication |
|
Type of lub-oil |
KCN 7805 (sulfur content<=200mg/m3) KCN 7810 (sulfur content <=460mg/m3) |
|
Overhauling time(H) |
≥36000 |
|
Manufacturer |
Jinan Diesel Engine Co.,Ltd |
|
Original |
China |
6. Technical Data of Alternator
|
Type |
1FC6 564-6LA42 (SIEMENS technology) |
|
Rated power(kW/kVA) |
1200/1500 |
|
Rated voltage(V) |
400 |
|
Rated frequency(Hz) |
50 |
|
Exciting method |
Brushless |
|
Wiring method |
3 phase 4 wire |
|
Number of pole |
6 |
|
Rated speed |
1000 r/min |
|
Insulation class |
Class F |
|
Class of protection |
IP23 to DIN 40050 |
|
Cooling |
A fan at the drive end draws the cooling air |
|
Type and number of bearing |
Rolling bearing, 2 pcs |
|
Coupling |
Elastic |
|
Original |
China |
7. The Component and Decontamination Requirement of Natural Gas
a. The component of natural gas (only for reference)
|
component |
CH4 |
C2H6 |
C3H8 |
C4H10 |
H2S |
N2 |
CO2 |
|
Content(%) |
≥76 |
<10 |
<8 |
<6 |
<0.1 |
<2 |
<1 |
b. Caloric Value: 21767kJ/Nm3 (5200kCal/Nm3)
c. Decontamination Requirement of natural gas
|
Composition |
Oil,Liquid |
Dust |
Dust Granularity |
Sulfide |
|
Content(mg/m3) |
No liquid state |
<30 |
<10μm |
<20 |
8. The Main Specification of Horizontal Radiator
|
Main Specification of radiator |
||
|
|
Low temperature system |
High temperature system |
|
Heat exchange area(m2) |
1040 |
520 |
|
Core quantity |
8 |
4 |
|
Dimension per core L×B×H(mm) |
1200×1200×88 |
|
|
Water capacity of radiator(L) |
346 |
257 |
|
Water capacity of expansion vessel(L) |
65 |
65 |
|
Main Specification of fan and motor |
||
|
Quantity of fan and motor |
8 |
4 |
|
Speed(rpm) |
960 |
960 |
|
Air flow rate(m3/min) |
593 |
593 |
|
Static pressure(Pa) |
287 |
287 |
|
Diameter of fan(mm) |
1065 |
1065 |
|
Motor parameter |
380V, 5.5kW, 3-phase 4-wire |
|
|
Protection class of motor |
IP55 |
|
|
Explosion-proof class |
dⅡ BT4 |
|
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.