16W Sensor DIM LED Driver With 300-900mA Current Output Daylight Priority Function
Product Features
- Conforms to ERP standard with micro-power consumption
- 5.8GHz ISM band, can be batch RED certified
- Isolated, flicker-free design with driver and sensor integrated
- Corridor function and light priority function for various applications
- Compact size for easy installation inside lighting fixtures
- All parameters adjustable via DIP switch
Technical Specifications
Input Parameters
| Voltage range |
220-240V AC, 50Hz/60Hz |
| Input current |
≤0.11A @ 230VAC |
| Inrush current |
≤15A (100us half-current) @230V AC |
| THD |
≤20%, 230VAC/Max Load |
| Power factor |
≥0.90, 230VAC/Max Load |
| Stand-by power |
≤0.5W |
| Working efficiency |
≥82%, @ 230V AC Max Load |
| Lightning surge |
L/N:1KV |
Output Parameters
| Working model |
CC |
| Type of load |
LED |
| Full load power |
16W Max |
| Flicker ripple |
Less than 2% |
| No-load output voltage |
60VDC Max |
| Load current |
300mA/400mA/500mA/600mA/700mA/800mA/900mA |
| Load output voltage range |
300mA (9-40V), 400mA (9-40V), 500mA (9-32V), 600mA (9-27V), 700mA (9-23V), 800mA (9-20V), 900mA (9-18V) |
| Constant current accuracy |
±5% @230VAC |
Sensor Parameters
| Operating frequency |
5.8GHz ±75MHz, ISM band |
| Transmitting power |
1mW |
| Detection Area |
25%/50%/75%/100% |
| Hold Time |
5S/1min/5min/10min |
| Stand-by Period |
0S/1min/10min/+∞ |
Daylight Sensor Parameters
| Daylight threshold |
5Lux/25Lux/50Lux/Disable |
| Daylight priority open/close |
Open: 5Lux/25Lux/50Lux | Close: 50Lux/100Lux/150Lux |
| Stand-by DIM Level |
15% |
| Detecting radius (sensitivity: 100%) |
Ceiling mounting 3m: 0.3m/S ≥4m, 1m/S ≥2.5m
Wall mounting 2m: 0.3m/S ≥10m, 1m/S ≥5m |
| Mounting Height |
3m Typical Value (6m Max) |
| 3db field angle |
90°@Xz flat, 95°@Yz flat |
Protection & Environmental Specifications
| Over voltage protection |
Yes, self-recovery |
| No-load protection |
Yes, self-recovery |
| Short-circuit protection |
Yes, self-recovery |
| Operating temperature |
-25…+50℃ |
| Maximum temperature (Tc) |
75℃ |
| Storage temperature/humidity |
-40℃…+80℃ Humidity: 85% |
| Withstand voltage |
3750Vac 5mA 60S (input "L N" to output SEC+ SEC-) |
Certifications & Standards
| Safety standards (LVD) |
EN61347-1, EN61347-2-13 |
| EMC standards |
EN55015, EN61547, EN61000-3-2, EN61000-3-3 |
| Environmental requirement |
Compliant to RoHS |
| Certificate |
CE RED |
| IP Rating |
IP20 |
| Protection class |
Class II |
Physical Specifications
| Wiring method |
Press terminal, wire diameter: 0.5-1.5mm² |
| Installation |
Built-in |
| Installation size |
Ф73mm × H23mm |
| Package |
PE bag clapboard, carton (K=A) |
| Net weight |
78±3g |
| Lifetime |
5 years warranty @Ta 230V full load |
The given values of detecting parameter is typical measured by 165cm high testers in an indoor open environment.
Operating Functions
On/OFF Function: Setting "stand-by period" to "0s", with other parameters adjusted according to practical applications.
3-step Dimming Function: Setting stand-by period to "30s/10min", with other parameters adjusted according to practical applications.
Daylight Priority Function: Setting stand-by period to "+∞", with other parameters adjusted according to practical applications.
Dimensions
Wiring Diagram
Internal Structure
Cut-out Dimensions
DIP Switch Settings
Detection Area
| Switch 1 |
Switch 2 |
Area |
| ON |
ON |
100% |
| ON |
- |
75% |
| - |
ON |
50% |
| - |
- |
25% |
Hold Time
| Switch 3 |
Switch 4 |
Time |
| ON |
ON |
5S |
| ON |
- |
1min |
| - |
ON |
5min |
| - |
- |
10min |
Daylight Sensor
| Switch 5 |
Switch 6 |
Daylight threshold |
Open/Close |
| ON |
ON |
5Lux |
5Lux/50Lux |
| ON |
- |
25Lux |
25Lux/100Lux |
| - |
ON |
50Lux |
50Lux/150Lux |
| - |
- |
Disable |
Disable |
Realizing daylight priority function when setting "stand-by period" to "+∞"
Stand-by Period
| Switch 7 |
Switch 8 |
Period |
| ON |
ON |
0S |
| ON |
- |
1min |
| - |
ON |
10min |
| - |
- |
+∞ |
Output Current
| Output current |
Output voltage |
Switch 1 |
Switch 2 |
Switch 3 |
Switch 4 |
| 300mA |
9-40V |
- |
- |
- |
- |
| 400mA |
9-40V |
- |
- |
- |
ON |
| 500mA |
9-32V |
- |
- |
ON |
ON |
| 600mA |
9-27V |
- |
ON |
- |
ON |
| 700mA |
9-23V |
- |
ON |
ON |
ON |
| 800mA |
9-20V |
ON |
ON |
- |
ON |
| 900mA |
9-18V |
ON |
ON |
ON |
ON |
Radiation Pattern
Ceiling Mounted Height: 3m Sensitivity: 100%/75%/50%/25%
Normal moving (Speed: 1m/s)
Slow moving (Speed 0.3m/s) - Note: There is no detection data at 25% sensitivity, 3m mounted height
Ceiling Mounted Height: 6m Sensitivity: 100%/75%
Normal moving (Speed: 1m/s)
Slow moving (Speed 0.3m/s) - Note: There is no detection data at 50%/25% sensitivity, 6m mounted height
Wall Mounted Height: 2m Sensitivity: 100%/75%/50%/25%
Normal moving (Speed: 1m/s)
Slow moving (Speed 0.3m/s)
Initialization
When powered on, the product automatically turns on light at 100% brightness. After 10 seconds, it turns off the light. During initialization, the product is not able to detect moving signals.
Factory Settings
Sensitivity: 100%; Hold Time: 5S; Stand-by period: 0S; Daylight Sensor: Disable.
Application Guidelines
- Installation should be performed by a professional electrician. Turn off power before installing, wiring, or changing DIP switch settings.
- Microwave sensors penetrate plastic and wooden objects well, but avoid metal accessories, metal shells, and glass shells near the antenna as they affect transmission and reception.
- Install microwave sensors at least 2m away from switches, routers, and other wireless devices to avoid radio interference (5G WIFI requires more than 2m distance).
- Keep the antenna surface away from input AC and output DC to avoid signal interference.
- Avoid installing near vibration equipment or moving objects, as vibration signals may trigger false detection. Keep away from large metal equipment, ventilation pipes, air conditioning outlets, exhaust vents, and smoke exhaust machines. Pets passing through may trigger the sensor.
- Suitable for indoor installation. For semi-outdoor or outdoor use, wind and rain may cause false triggers. In metal fixtures or narrow environments, reduce sensitivity or contact manufacturer.
- Wall mounting significantly increases detection distance - reduce sensitivity or contact manufacturer for support.
- Product specifications may change without prior notice due to continuous improvements.
- Sensitivity area depends on object movement speed, object size, mounting height, mounting angle, working environment, and reflecting materials.
- Daylight sensor values are measured in sunny environments without shadows and with ambient light diffuse reflection. Actual illuminance values may vary by environment, time, season, and climate.