strong Private Prepaid Electricity Meters for Submetering Tenants CA368 and STS Compliant
The CA368 is a solid state, standalone three phase four wire keypad based prepayment meter finished in a compact BS footprint housing. It is ideal for residential commercial and light industrial environments.
The meter is manufactured in accordance with ISO9001 standards and IP54 protection rating. It measures both active and reactive energy.
Strong private prepaid electricity meters for submetering tenants, CA368 and STS compliant.
The CA368 is a solid-state, standalone, three-phase, four-wire, keypad-based prepayment meter with a compact BS footprint housing. It is ideal for residential, commercial, and light industrial environments.
The meter is manufactured in accordance with ISO 9001 standards and has an IP54 protection rating. It measures both active and reactive energy.
- STS compliance
- bi-directional measurement for significant reverse energy (SRE);
- A maximum current of 100 A per phase
- a compact meter design with a British Standard layout.
- Tamper detection.
- Programmable software power limit
- Advanced commissioning/decommissioning feature
- Prepayment/credit mode
- Large display with language-independent icons
- High surge withstand capability for areas prone to lightning or other line surges.
- Compliant with 1524, IEC 62052-11 and IEC 62053-21
- Maximum demand measurement
- The meter provides detailed power information such as phase voltage, current, total active power, reactive power, apparent power, total power factor and power grid frequency.
- Easy to install and ideal for new reticulation, as well as retrofitting credit meters with BS footprints.
- The meter provides valuable information to help consumers manage and budget their electricity consumption effectively.
- The IEC 62056-21 compliant optical and RS485 ports allow for easy data interrogation.
- Communication capability is expandable to support AMR and AMI facilities.
- Advanced load control and disconnection features
- Tamper detection and event recording, such as cover opening, reverse connection and blackout.
| Nominal voltage Un | 3x240V |
| Limited voltage | 60%~120%Un |
| Frequency | 50/60Hz+5% |
| Basic current(Ib) | 10A |
| Maximum current(Imax) | 100A |
| Starting current(Ist) | 30mA |
| Active energy constant | 400imp/kWh |
| Accuracy | |
| Active energy to IEC62053‐21 | Class1.0 |
| Reactive energy to IEC62053‐23 | Class2.0 |
| Power Consumption | |
| Power consumption in Voltage circuit | <2W <8VA |
| Power consumption in current circuit | <1VA |
| Temperature range | |
| Operation meter | 25℃ to+70℃ |
| Storage | 40℃ to+85℃ |
| AC Insulation strength | 4kV at 50Hz during 1min |
| Impulse voltage 1.2/50μs mains connections | 8kV |
| Electrostatic discharges | |
| Contact discharge | 8kV |
| Air discharge | 16kV |
| Electromagnetic RF fields | |
| 27MHz to 500MHz typical | 10V/m |
| 100kHz to 1GHz typical | 30V/m |
| Fast transient burst test | 4kV |
| Protection Rating | IP54 |
| Insulation Classification | Protective Class II |
| Maximum cable size | 10 mm |
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.