FM200/Heptafluoropropane/HFC-227ea Pipe Network Gas Cylinder 40L/70L/100L/120L/180L/245L

Price Negotiable
Price: Pricing based on quantity
MOQ: 5 set
Delivery Time: 15-20days
Brand: XINGJIN
Product Description

FM200 Pipe Network Gas Cylinder


Overall system introduction:
  The HFC-227ea automatic fire extinguishing system consists of a fire extinguishing agent bottle group, a bracket, a drive gas bottle group, a container valve, a liquid check valve, a gas check valve, a drive device, a gas transmission control pipeline, a manifold, a selection valve, a tee, a reducing tee, an elbow, a reducing elbow, a flange, a safety valve, a signal feedback device, a pipe network, a nozzle, a reagent, a fire detector, a gas fire extinguishing controller, an audible and visual alarm, an alarm, a deflation indicator light, an emergency start/stop button, etc.

Fire Extinguishing Agent Cylinder Set
1) Purpose:
Used to store HFC-227ea fire extinguishing agent, with functions such as sealing, releasing, filling, overpressure relief, and pressure display.
2) Structure: Consists of a container valve, siphon tube, and storage container. The storage container is a refillable, red epoxy-painted, welded steel container. The container valve consists of a valve body, actuating device, a piston, a pressure indicator, and a pressure relief device. After connecting to the siphon tube, it is installed on the mouth of the storage container. The container valve can be opened pneumatically or manually to release the fire extinguishing agent.
3) Main Technical Parameters:
 

Model specifications Storage pressure

Volume

(L)

Container Valve

Model

Nominal diameter

(mm)

Equivalent length
(m)

Outer diameter

(mm)

H
(mm)

Net weight

(Kg)

QMP70/5.6 5.6MPa 70 QRF32/8 32 6 267 1560 86
QMP90/5.6 5.6MPa 90 QRF32/8 32 6 325 1440 130
QMP120/5.6 5.6MPa 120 QRF32/8 32 6 325 1600 139
 

4) Installation and Instructions:
1) The installation location should comply with the requirements of the design documents and be arranged in the order of the cylinder group numbers. The height difference should not exceed 20mm, and the distance between the operating surface and the wall or between operating surfaces should not be less than 1.0m.
2) In an emergency, remove the safety pin on the actuator, engage the handle one by one, and activate the cam lever to open all the container valves to release the fire extinguishing agent.
5) Maintenance Instructions:
Perform a monthly visual inspection to ensure there is no deformation or mechanical damage from impact, no surface rust, an intact protective coating, and the safety pin and seal are intact before continuing to use.
6) Note:
The safety pin on the container valve is used to lock the cam lever. Pulling out the safety pin before disengaging the cam lever is necessary only for manual actuation of the container valve. Locking the cam lever does not affect the nitrogen actuation of the container valve.

Detailed parameters:

Specification inner diameter Bottle thread Valve outlet aperture Bottle height Bottle + container valve height Total height of bottle + container valve + solenoid valve
40L*5.6MPa ø300 M80*2 50 757±15 897±15 1057±15
70L*5.6MPa ø350 M80*2 50 898±10 1038±10 1198±10
100L*5.6MPa ø350 M80*2 50 1213±10 1353±10 1513±10
120L*5.6MPa ø350 M80*2 50 1414±10 1554±10 1714±10
150L*5.6MPa ø400 M80*2 50 1395±10 1535±10 1695±10
180L*5.6MPa ø400 M80*2 50 1630±10 1770±10 1930±10
70L*17.2 ø267 PZ56 32 1499±10 1679±10 /
90L*17.2 ø325 PZ56 32 1420±10 1600±10 /
120L*17.2 ø325 PZ56 32 1835±10 2015±10 /


Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Guangzhou Xingjin Fire Equipment Co.,Ltd.
Location Room 703&704, N0.3 Building, NO.8 Lianyun Erheng Road, Shiqi Town, Panyu District, Guangzhou, China
Contact Person Anna

Request A Quote

Please check your email address.
Your message must be at least 20 characters.