132kV Porcelain Housing Lightning Arrester Y10W5-132 for Substations
Price:
1
MOQ:
3
Delivery Time:
Negotiable
Product Description
132kV Porcelain Housing Surge Arrester - Model Y10W5-132
Product Specifications
| Attribute | Value |
|---|---|
| Model NO. | Y10W5-132 |
| Installation | Parallel Arrester |
| Application | Substation |
| Size | Large |
| Operation Voltage | High Voltage |
| Material | ZnO |
| Creepage Distance | 4250mm |
| Housing | Porcelain |
| Line Discharge Class | 3 |
| Specification | IEC 60099-4 |
Key Features
- Superior electrical performance and reliability
- Lightweight design for easier installation
- Explosion and shatter proof construction
- Excellent performance in polluted environments
- Vandalism resistant design
- Moisture ingress protection
- High mechanical strength
- UV radiation insensitive
- Excellent resistance to ozone and corona
- Superior tracking resistance
Technical Parameters
| Rated voltage | 132kV |
| Height | 1970mm |
| Creepage distance | 4250mm |
| Maximum system voltage Um | 145/161KV |
| Line discharge level | 2/3/4 |
| Long duration current impulse | 600/800/1000A |
| 4/10 μs current impulse | 100KA |
| Lightning impulse withstand | 650KV |
| Power frequency voltage withstand | 275KV |
Detailed Specifications
| Parameter | Value |
|---|---|
| MCOV (kV) | 106 |
| Nominal Current (kA) | 10 |
| Residual voltage of steep impulse at 5kA (kV) | 396 |
| 8/20µS Residual voltage of lightning impulse current (Peak value) at 5kA (kV) | 334 |
| Residual voltage of switching impulse current (peak value) at 1kA (kV) | 263 |
| 1mA D.C reference voltage (kV) | 192 |
| 2mS long duration impulse current (A) | 850 |
| 4/10µS High current impulse (kA) | 100 |
Product Images