Shanghai Shenghua Cable (Group) Co., Ltd.
                                                                                                           
Verified Supplier
29 Years
Since 1997
Menu

Black XLPE Insulated Aerial Bunch Cable For Overhead Distribution Lines

Price Negotiable
Price: 0.19-10.99USD/M
MOQ: 1000m
Delivery Time: 15 Days
Brand: SHANCABLE
Product Description

Black XLPE Insulated Aerial Bunch Cable For Overhead Distribution Lines

 

 

 

Detailed Product Description

ABC cable
(Service drop cable)

1. Stranded aluminium conduct

2. PE or XLPE insulation
3. ACSR, AAAC Messenger wire

 

Application

 

It is preferred to use of service drop (ABC cables) instead of uninsulated conductors
at low voltage networks. service drop (ABC cables)are especially used at areas
where the cost of underground networks is expensive and also
for electrification of rural areas like villages.

Voltage

Rated voltage U0 / U = 0.6 /1 kV
VAC test voltage 5 kV

Technical Data
Maximum operating temperature 90 degree
Maximum short-circuit temperature 250 degree. Service drop( ABC cables) are especially used at areas where the cost of underground networks is expensive and also for electrification of rural areas like villages.

ABC technical charaters based on Standard ASTM ANSI/ICEA S-76-474 and NFC 33-209

 

 

Schedule of technical particulars

 

Phase conductor                  
Nominal cross-sectional area mm² 25 35 50 70 95 120 150 185
Number of cores   3 3 3 3 3 3 3 3
Minimum number of wires   6 6 6 12 15 15 30 30
Nominal insulation thickness mm 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0
Diameter of insulated core mm 8.5 9.5 11.2 13.0 15.1 16.6 18.4 20.6
Max. DC resistance at 20℃ ohm/km 1.20 0.868 0.641 0.443 0.320 0.253 0.206 0.164
Current rating at still wind, ambient A 84 104 129 167 209 246 283 332
temperature=30℃
Conductor temperature=75℃                  
Messenger conductor                  
Nominal cross-sectional area mm² 25 25 35 50 70 70 95 120
Minimum number of wires   6 6 6 6 12 12 15 15
Nominal insulation thickness mm 1.2 1.2 1.2 1.4 1.4 1.4 1.6 1.6
Diameter of insulated core mm 8.5 8.5 9.5 11.2 13.1 13.1 15.1 16.6
Max. DC resistance at 20℃ ohm/km 1.312 1.312 0.943 0.693 0.469 0.469 0.349 0.273
Calculated breaking load kN 6.4 6.4 8.9 12.1 18.0 18.0 24.2 30.8
Street lighting conductor                  
Nominal cross-sectional area mm² 25 25 35 50 70 70 95 120
Minimum number of wires   6 6 6 6 12 12 15 15
Nominal insulation thickness mm 1.2 1.2 1.2 1.4 1.4 1.4 1.6 1.6
Diameter of insulated core mm 8.5 8.5 9.5 11.2 13.1 13.1 15.1 16.6
Max. DC resistance at 20℃ ohm/km 1.312 1.312 0.943 0.693 0.469 0.469 0.349 0.273
Completed cable                  
Approx. overall diameter mm 23.2 25.6 30.0 34.9 40.6 44.1 49.2 54.9
Approx. weight of cable kg/km 470 560 740 980 1330 1580 1940 2410
Packing length m/drum 1000 1000 1000 1000 500 500 500 500

 

 

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Shanghai Shenghua Cable (Group) Co., Ltd.
Location No.7577 Hunan Road, Pudong New District. Shanghai China
Contact Person Mayling Zhao

Request A Quote

Please check your email address.
Your message must be at least 20 characters.