ACSR conductors have been widely used in power transmission lines with various voltage levels,because they have such good characteristics as simple structure,convenient installation and maintenance,low cost large transmission capacity.And they are also suitable for laying across rivers valleys and the places where special geographical features exist.

 

Shanghai Shenghua Cable (Group)Co.,Ltd.
Test Report
Specification : ACSR1033.5MCM Ortlan Item: Aluminum Conductor
Steel Reinforced
Standard: ASTM B 232 Date: 2017.1.5
No. Item Standards and Requirements Test Results Evaluation
1 Dimension of conductor
1-1 Overall Diameter mm 30.81±1% 30.82 Qualified
1-2 Number of AL. wire 45 45 Qualified
1-3 Number of steel wire 7 7 Qualified
1-4 Diameter of Al.wire (mm) 3.85±1% 3.850 3.852 3.858 Qualified
1-5 Diameter of steel wire (mm) 2.57±0.051 2.572 2.580 2.604 Qualified
1-6 Stranding direction Rightward Rightward Qualified
1-7 Appearance The surface of the stranded wire is smooth, glossy and tightly stranded Meet the requirement Qualified
2 Lay ratio
2-1 Lay ratio of steel wire 18-30 18.1 Qualified
2-2 Lay ratio of 12 wire layer 10-17 15.8 Qualified
2-3 Lay ratio of 18 wire layer 10-16 13.6 Qualified
2-4 Lay ratio of 24 wire layer 10-13 11.3 Qualified
3 Performance of steel wire
3-1 Tensile strength MPa ≥1340 1410 Qualified
3-2 Elongation(250mm) % ≥3.5 3.6 Qualified
3-3 Stress at 1% extension MPa ≥1280 1302 Qualified
3-4 Mass of Zinc coating g/m2 ≥229 254 Qualified
3-5 Zinc coating adherence No crack Meet the requirement Qualified
3-6 Wrapping test The wire shall be wrapped around 1 time the diameter of the wire, from a close helix of eight turns,
wire shall not crack
Meet the requirement Qualified
4 Performance of aluminum wire
4-1 Tensile strength MPa (after) ≥160 163 Qualified
4-2 Wrapping test The wire shall be wrapped around 1 time the diameter of the wire, from a close helix of eight turns, withdraw six turns, wire shall not crack Meet the requirement Qualified
4-3 D.C. resistivity at 20℃ Ω.mm2/m ≤0.028264 0.027812 0.027902
0.027721 0.027825
Qualified
5 Performance of conductor
5-1 Tensile strength kN ≥123.1 124 Qualified
5-2 D.C. resistance at 20℃ Ω/km ≤0.05531 0.049 Qualified
5-3 Weight kg/km 1732 1732.1 Qualified
5-4 Lay direction Rightward Rightward Qualified
Conclusion: The performances tested meet the technical requirements of ASTM B 232, IEC 60888, IEC 60889. Permission to deliver the products.
           
Tested by:   Checked by:   Approved by:  

 

 

 

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Shanghai Shenghua Cable (Group) Co., Ltd.
Location No.7577 Hunan Road, Pudong New District. Shanghai China
Contact Person Mayling Zhao

Request A Quote

Please check your email address.
Your message must be at least 20 characters.