KTO 011 Thermostatic Bimetal Thermostat NC Heating NO Cooling Small Compact
KTO 011 NC Heating KTS 011 NO Cooling Small Compact Thermostatic Bimetal Thermostat
NTL 10A-F / NTL 10A-M: Thermostat (normally closed); contact breaker for regulating heaters. The contact opens when temperature is rising.
NTL 10B-F / NTL 10B-M: Thermostat (normally open); contact maker for regulating of filter fans and heat exchangers or for switching signal devises when temperature limit has been exceeded. The contact closes when temperature is rising
|
KTO 011/KTS 011 |
|
|
Switch temperature difference |
+/-5°C |
|
Sensor element |
thermostatic bimetal |
|
Contact type |
snap-action contact |
|
Service life |
>100,000 cycles |
|
Max. switching capacity |
250VAC, 10 (2) A / 120VAC, 15 (2) A DC 30W at 24VDC to 72VDC |
|
Max. inrush current |
AC 16A for 10 sec. |
|
Connection |
2-pole terminal, clamping torque 0.5Nm max.: rigid wire 2.5mm² (AWG 14)stranded wire¹ 1.5mm² (AWG 16) |
|
Mounting |
clip for 35mm DIN rail, EN 60715 |
|
Casing |
plastic according to UL94 V-0, light grey |
|
Dimensions |
60 x 33 x 43mm |
|
Weight |
approx. 40g |
|
Fitting position |
variable |
|
Operating/Storage temperature |
-45 to +80°C (-49 to +176°F) |
|
Operating/Storage humidity |
max. 90% RH (non-condensing) |
|
Protection type |
IP20 |
¹ When connecting with wires, wire end ferrules must be used.
Important note: The contact system of the regulator is subjected to environmental influences, thus the contact
resistance may change. This can lead to a voltage drop and/or self-heating of the contacts.