UL910 NFPA262 Steiner Tunnel Flame Test Furnace for Cable Flame Spread Smoke Density SL-910
The SL-910 Steiner horizontal tunnel furnace is a dedicated combustion test system for evaluating the flame spread and smoke density of electrical and optical-fiber cables in accordance with UL 910 / NFPA 262 standards.
This integrated system combines ignition sequencing, combustion safety, electrical interlocking, automatic temperature control, manual adjustment, monitoring & alarm functions, and data acquisition into one comprehensive unit. The system is controlled by an OMRON PLC together with Advantech hardware and Visual Basic software.
Design Specifications
| Furnace Type | Steiner horizontal tunnel furnace |
| Chamber Size (L x W x H) | 7620 x 451 x 305 mm |
| Working Temperature | Maximum 600°C (flue gas) |
| Fuel | Methane, purity not less than 95% |
| Fuel Heat Value / Pressure | 3500 Btu/lb / 0.4-0.5 MPa |
| Burner | 3/4 inch U-shaped double-head burner |
| Flue Gas Temperature | Below 250°C, normally below 200°C |
| Shell / Frame Material | SUS304 stainless steel 3 mm / Q235-A square & rectangular tube |
| Refractory Brick | 229 x 114.5 x 64 mm, max 1427°C, density 0.77±0.046 g/cm³ |
| Observation Window | Quartz + tempered glass double layer, 3 mm, 70±6 x 280±38 mm |
| Exhaust Duct | 406 mm ID, SUS304, 1.5 mm thick |
| Smoke Density System | US GE sealed lamp 12 V, photocell, optical path 914±51 mm |
| Air Velocity | 1.22 m/s ±0.025 |
| Heat Release Adjustment | 86 kW ±2 kW (294,000 ±7,300 Btu/hr) |
| Thermocouple | 19 AWG nickel-chrome (K-type) |
| Control System | OMRON controller + Advantech + Visual Basic |
| Reference Material | TP149 standard cable |
| Power Supply | 220 V / 380 V, 50 Hz |
Installation Requirements
- The fire test room must allow free air flow and maintain a controlled positive pressure of 0-12 Pa (0-0.05 inch water column) above ambient pressure throughout each test
- Ambient temperature 18.3-26.7°C and relative humidity 45-60%; air conditioning and humidification/dehumidification equipment required
- Site dimensions: length not less than 12 m, width not less than 8 m, height not less than 4 m
- Cooling water: tap water, 0.07 MPa pressure
Similar Products
Related Videos
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.
Company
SKYLINE INSTRUMENTS CO.,LTD
Location
No.1802 Room 6# Building Universal Commerce Center Nancheng District Dongguan Guangdong China
Contact Person
Ivy Xie