Rogowski Coil Flexible Current Clamp 6000A AC Clamp -20 - 70 ° C Operating Temp
Price:
Negotiable
MOQ:
1 Piece
Delivery Time:
Negotiable
Brand:
GFUVE
Product Description
Flexible Rogowski coil 6000A AC current sensor / Inductive Current Clamp
The FQ-RCT02 FlexibleAC current sensor are designed for easy installed in tight spaces and without the need for dismantling the primary busbar or cables ..
APPLICATIONS
- Power quality monitoring
- Power meters
- Smart logger
- Energy sub-meters
- Distributed measurement systems
PARAMETERS
| Electrical parameters | |||||||
|---|---|---|---|---|---|---|---|
| Model | FQ-RCT02-120 | FQ-RCT02-190 | FQ-RCT02-305 | FQ-RCTA02-120 | FQ-RCTA02-190 | FQ-RCTA02-305 | |
| Current range | 10A~30kA | 10A~6000A | |||||
| Frequency | 25Hz~20kHz | 45Hz~600Hz | |||||
| Output voltage | Rated current | 1000A | 2000A | 3000A | 1000A,1500A, 2000A,3000A | 2000A,3000A, 5000A,6000A | 3000A,4000A, 5000A,6000A |
| 50Hz | 100mV AC | 200mV AC | 300mV AC | ||||
| 333mV 1mV/A@1000-3000A(0.5mV/A@4000-6000A) |
|||||||
| Max output | / | 3.0V AC max | |||||
| Accuracy | <1% @25°C (45-65Hz) | <1% @25°C (45-65Hz) | |||||
| Phase error | <60’ @25°C (45-65Hz) | <60’ @25°C (45-65Hz) | |||||
| Output sensitivity | ±2% Max (No Calibration) ±0.5% @25°C (With Calibration) |
1% | |||||
| Linearity error | ±0.2% (10%-100%I1n) | ±0.2% | |||||
| Position sensitivity | ±2% | ±2% | |||||
| External influence | ±2% Max | ±1.5% Max | |||||
| Power supply | / | 10-30VDC,30mA Max. | |||||
Similar Products
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.
Company
Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
Location
Oriental HuaRui A, No. 150 Guanzhuang Road, Chaoyang District, Beijing, 100024, China
Contact Person
Andy