Thermal Printer Electrical Test Equipment Circuit Breaker Tester / Analyzer
T-209 Circuit Breaker Tester With Thermal Printer
T-209 Circuit Breaker Tester can test the vacuum circuit breaker ,sf6, oil circuit breaker, gis and etc. the test parameters include, close or open time ,delta time ,bounce time ,bounce cycles, multi-operation, stroke , gap ,over-travel ,overshoot ,rebound and the speed, with the ability of test results and graph display.
The CB Analyzer tm system, is a new circuit breaker testing method that utilizes a Windows software program on a laptop or tablet pc to determine the condition of all types of circuit breakers.. The system combines vibration analysis, internet data transfer and sophisticated, condition-based analysis together with an online equipment database to easily and quickly test your circuit breakers .
Circuit breaker testing typically focuses on performing motion and time measurements on the units. However, our testing solutions have revolutionized circuit breaker testing. The testing solutions we offer include systems that can supply power during the testing process and are capable of measuring the micro-ohm resistance across the closed contacts.
Function & Features
- Immunity : withstand the 550KV electrostatic environment .
- Transducer : with one analog transducer test ability .
- Standard : with the standard of DL/T846.3—2004 (P.R.C.)
- Power : with internal dc power ,the voltage ranges from 15v to 250v.
- Trigger : with four triggers to start the recording ,channels state, voltage, current and transducer.
- HMI : via keypad and a large transflective LCD display (320 x 240 pixels).
- Speed :supply series of speed definition with editable and un-editable selection.
- Recording: with twelve channels ,coil current and transducer .
- Print :with internal installed 58mm wide thermal printer.
- Communication:with RS232 and USB communication interface.
- Memory: with a SD card of 2GB,the maximum storage ability is 100 test results.
- USB FLASH: USB and RS232 interface for data communication with the PC.
- Help : the instrument has internal help topic .
Technical Data
| Product Model | T-209 |
| Rated working condition |
Operating temperature: - 10℃ to 50℃; storage: - 20℃ to + 70℃. Relative humidity : 5 - 95%, without condensing. |
| Input power | AC 220V/240V±10% AC, 50Hz/60Hz + 10% |
| Immunity | withstand the 550KV electrostatic environment |
| Test channels | 12 channels with 25V,the current is 50mA |
| Transducer | one analog transducer |
| TIME |
Recording time length : 0~9.9s Time accuracy : ±0.l%reading ± 2 LSB Resolution : 0.1ms |
| Motion |
Range : 0~1000mm Accuracy : ±1% reading ±1LSB Resolution : 0.1mm |
| Velocity |
Ranges : 0~20.00m/s Accuracy :±1%reading ±1LSB Resolution : 0.01m/s |
| DC POWER |
Ranges : 15~260V Max current : 20A Accuracy : ±1%reading ±1LSB Load change :≤1% |
| TRIGGER |
Voltage : 15~260V Current : 0.1-20A Tranducer : the transducer states changes Channels : channels states changed |
| Memory | SD card of 2GB,the maximum storage ability is 100 test results. |
| LCD | 5.7″black and white LCD display (320 x 240 pixels) |
| Communication | RS232 and USB communication interface |
| Printer | internal installed 58mm wide thermal printer. |
| Standard | DL/T846.3—2004 (P.R.C.) |
| DIMENSIONS | 380mm×262mm×120mm |
| WEIGHT | 6kg |