6 Phase Current Voltage Protective Relay Test Set With GPS Function

Price Negotiable
Price: Negotiable
MOQ: 1 Set
Delivery Time: 7 Days
Brand: GFUVE
Product Description

 

TEST-630 GFUVE 6 phase current voltage Protective Relay Test Set With GPS function

 

 

The GFUVE Protection Test Set TEST-630 Protective Relay Test System is the first all-in-one relay test system with a direct front panel interface for all functions, without exception! The ideal integrated system for testing and calibration of protection and control relays, simulation of power system phenomena, and verification of voltage, current, phase, and power transducers.
Breeze through single overcurrent relays to multi-terminal end-to-end schemes with this one box. No add-ons, no hidden costs. All the brute force power (VA) that you need for old electromechanical relays; and for modern microprocessor-based relaying, all the powerful functions that you need, simplified by built-in intelligence capabilities. Increase your protection system reliability confidence with realistic transient waveform and GPS time-synchronized testing to mimic real-world conditions.

 

TEST-630  (6*30A, 6*130V) is a powerful secondary injection test set with 6-currents and 6-voltages sources.This advanced secondary injection kit is capable of testing differential relay and synchronizing relay. Optional upgrade is available to support the test of all kinds of relay and protection devices.

 

Parameters

 

Electrical parameters  
Allowable range AC220V±10% or AC110V±10%, 50/60Hz±10%
Time measurement 0.1ms-999999.999s
AC current output  
Phase current output (effective value) 6×0-30A or 3 × 0-60A
Maximum output power 520VA/phase
Maximum parallel current output (effective value) 0-180A
Long-term allowable working value of phase current (effective value) >10A
Allowable working time of maximum current >11s
Accuracy <±0.2%
AC voltage output  
Phase voltage output (effective value) 6×0-130V
Line voltage output (effective value) 0-260V
Maximum output power 70VA/phase
Accuracy <±0.2%
DC voltage output  
Output range 0-300V or 6×0-±130V
Maximum output power 130VA
Accuracy <±0.2%
DC current output  
Output range -10-10A or 6×0-±10A
Maximum output power 150VA
Accuracy <±0.2%
Binary input  
Idle contact 1-20mA, 24V (DC)
Electric potential contact 0-250V (DC)
Binary output  
Idle contact 250V/0.5A (DC)
Rated output  
Frequency error <±0.01HzHz
Phase error <±0. 1°
Waveform distortion <±0.3% (fundamental wave)
Time error <40µs
Output frequency 0-1050Hz
Superposed harmonic wave 0-21times
Time measurement  
Test range 0.1ms-999999.999s
Mechanical parameters  
Dimensions (L×W×H) (mm) 360×195×365
Weight (kg) 19.6
Environmental conditions  
Use range 0°C to 45°C
Storage range -25°C to 70°C

 

Test Item

 

1 . U/I Test
2 . DC Test
3 . Impedance Characteristics
4 . Power Direction Test
5 . I-T Test
6 . Differential Relay
7 . Harmonic Test
8 . Differential Protection
9 . Distance Protection
10 . Zero Sequence Protection
11 . Setting Group Test
12 . State Sequence
13 . Synchronization Test
14 . Special Test
15 . Oscillation Test
15 . Metering Instrument
16 . Hardware Checkout
17 . Low Voltage Protection

 

 

 

Product Photo:

 

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
Location Oriental HuaRui A, No. 150 Guanzhuang Road, Chaoyang District, Beijing, 100024, China
Contact Person Andy

Request A Quote

Please check your email address.
Your message must be at least 20 characters.