Modbus RTU RS485 Internet Three Phase Power Meter Panel Mounting 500g Weight

Price Negotiable
Price: Negotiable
MOQ: 1 Piece
Delivery Time: Negotiable
Brand: GFUVE
Product Description

Three Phase Modbus RTU RS485 Internet Panel Mounting Digital Stages Power Meter With Data Logger

 

 

FU2200A 0-480V digital stages power meter with PC software is a three-phase multifunction power and energy meter manufactured by GFUVE. It provides excellent value for monitoring power and energy management systems. It may be used as data gathering devices for intelligent power distribution or plant automation systems. All monitored data is available via a standard digital RS485 communication port, which is based on the Modbus RTU protocol.

 

A highly specialized 3 phase meter with power quality tools such as waveform capture, event logging and more. The Acuvim IIW meter is ideal for granular 3 phase metering.


A three-phase power meter needs to deal with more current and voltage information compared to a single-phase power meter and requires analog input for a maximum of seven channels and high processing capacity for power calculation. Further, the smart power meter needs to meet the security requirements of the DLMS international standard and so on.

 

 

Features

 

  • True-RMS measuring parameters
  • ANSI and IEC 0.5s accuracy class
  • Power quality analysis
  • 4 quadrant energy
  • 2MB onboard memory, can be extended to 16M
  • Data logging
  • High-speed RS485, Ethernet port (option)
  • Measure individual harmonics from 2nd to 63th (option)
  • TOU, 4 Tariffs, 6 Seasons, 6 Schedules
  • Three years warranty
  • With PC management software; web browse data

 

 

Parameters
 

 

Electrical parameters
Power Supply (AC/DC) AC85-400V / DC85-330V
Power consumption: <4VA
Measurement Parameters Voltage (Ph-N); Voltage (Ph-Ph); Current; Frequency; PF;
Active Power(W); Reactive Power(Q); Apparent Power(S),
2nd to 63th harmonics(option)
Harmonics Total harmonics ratio of phase-voltage
Total harmonics ratio of current
2nd to 63th harmonics ratio of phase-voltage
2nd to 63th harmonics ratio of current
Maximum Value & Minimum Value Voltage, current, frequency, active power, reactive power, apparent power,demandP,demandQ, demandS.
Computation Forward active power energy
Reverse active power energy
Forward active power energy
Reverse reactive power energy
Measuring Range 0-480V, 0-10A, 45-65Hz, -1 ~ 0 ~ 1
Measuring Accuracy Voltage: 0.5%RD±0.05%FS
Current: 0.5%RD±0.05%FS
Active Power: 0.5%RD±0.05%FS
Reactive Power: 1.5%RD +0.05%FS
Apparent power: 0.5%RD +0.1%FS
Power Factor: 0.5%RD
Frequency: 0.05%RD
Active Energy: 0.5s
Maximum Demand Ia, Ib, Ic, ΣPtotal, ΣQtotal, ΣStotal, 15 minutes
Display Blue back-lit LCD Display
5 display figures
4 operation keys
Communication Support RS-485 interface port, 32 (128) Networking
ModBus-TCP/IP SNMP communication protocol
Ethernet 10/100M port (RJ45)
Memory 2M onboard memory,can be extended to 16M.
Data looger interval can set by end users from 1min to 60min.The default is 15min.
You can read the data through a PC, also you can select the data to diaplay and store from software.
Programmable Measuring system: 3P4W/3P3W etc
Transformation Ratio: PT 1-10000; CT 1-10000
Energy Pulse Provides active & reactive energy pulse output
Pulse parameters can be choosed
Range: 0.1-10000kWh/kvarh
Dry contact output ( 1A x 100V )
Connection Mode 3P4W, 3P4W BAL, 3P3W, 3P3W BAL, 1P3W, 1P2W
Baud 1200-57600, Standard 38400
Mechanical parameters
Dimensions    ( L x W x H ) ( mm ) 96x96x12.8
Mounting Panel mounting
Trepanning: 92x92mm
The thickness of installation: 51mm
Environmental conditions
Temperature -5 to +50 °C
Humidity 20%-95%RH, without condensation
Warranty Three years warranty

 

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
Location Oriental HuaRui A, No. 150 Guanzhuang Road, Chaoyang District, Beijing, 100024, China
Contact Person Andy

Request A Quote

Please check your email address.
Your message must be at least 20 characters.