TEST-330 THREE PHASE RELAY PROTECTION MICROCOMPUTER TEST SYSTEM

Test-330 is a three phase current output and five phase voltage output relay tester with embedded host machine equipped with Complex Programmable Logic Device.

 
 

FEATURES

  • Three phase current output
  • Five phase voltage output
  • Accuracy class 0.2%
  • Embedded host machine equipped with Complex Programmable Logic Device (CPLD)
  • Eight-path synchronous D/A output in a single machine
  • High-accuracy linear power amplifier
  • Host machine integrated single cabinet structure with big LCD screen and complete interface has obtained appearance patent
  • Intelligent self-protection function
  • Plentiful Binary and powerful software function
  • Easily complete the ABB, Siemens, AREVA, Schneider, GE, SEL, VAMP, Toshiba, NR, Sifang and other foreign manufacturers of protective device test
  • Synchronous output of five-phase voltage and three-phase current, Max AC current output is 90A, Max AC voltage output is 260V
 
 

OVERVIEW

  • Three phase current output
  • Five phase voltage output
  • Accuracy class 0.2%
 

TEST ITEM

  • U/I test
  • DC test
  • Impedance characteristics
  • Power direction test
  • I-T test
  • Differential relay
  • Harmonic test
  • Differential protection
  • Distance protection
  • Zero sequence protection
  • Setting group test
  • State sequence
  • Synchronization test
  • Special test
  • Oscillation test
  • Metering instrument
  • Hardware checkout
  • Low Voltage protection
  • Fault Recurrence
 

PARAMETERS

Electrical parameters
Power voltage AC220V±10% or AC110V±10%, 50/60Hz±10%
Time measurement 0.1ms-999999.999s
AC current output 
Phase current output (effective value) 3 x 0-30A
Maximum power output 260VA/phase
Maximum parallel current output (effective value) 0-90A
Long-term allowable working value of phase current
(effective value)
>10A
Allowable working time of maximum current >11s
Accuracy class <±0.2%
AC voltage output 
Phase voltage output (effective value) 5 x 0-130V
Line voltage output (effective value) 0-260V
Maximum power output 70VA/phase
Accuracy class <±0.2%
DC current output 
Output range -10 to 10A or 3 x 0 to ±10A
Maximum power output 200VA
Accuracy class <±0.2%
DC voltage output 
Output range 0-300V or 5 x 0 to ±130V
Maximum output power 130VA
Accuracy class <±0.2%
Binary input 
Idle contact 1-20mA, 24V (DC)
Electric potential contact 250V/0.5A (DC)
Binary output 
Idle contact 250V/0.5A (DC)
Rated output 
Frequency error <±0.01Hz
Phase error <±0.2°
Waveform distortion <±0.3% (fundamental wave)
Time error <40µs
Output frequency 0-1050Hz
Superposed harmonic wave 0-21times
Mechanical parameters 
Dimensions (L×W×H) (mm) 360x195x375
Weight (kg) 16.6
Environmental conditions
Use range 0°C to 45°C
Storage range -25°C to 70°C

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
Location Oriental HuaRui A, No. 150 Guanzhuang Road, Chaoyang District, Beijing, 100024, China
Contact Person Andy

Request A Quote

Please check your email address.
Your message must be at least 20 characters.