Single Phase Ac Electrical Test Equipment Clamp Meter Calibrator High Performance
GF6018A multimeter and clamp meter calibrator
The equipment is compliance with national verification regulation: JJG124-2005 “Ammeter, voltmeter, power meter and resistance meter verification rules” and related national standards. 0.05 single-phase AC/DC standard source, can verify magnitude 0.2 and the following AC/DC voltmeter, ammeter, frequency meter, resistance meter. The source signals by using DSP and 16-bit high-speed analog-to-digital converters of controllable sine wave, the distorted wave signal source.The equipment comes with RS-232 interface, can be connected with PC to a semi-automatic verification system. It has precise interface and multi-functions including verification, storage and query.The equipment adopts color LCD screen, chart character display is clear, with high precision, stable and reliable, convenient operation and flexible characteristics.
FEATURES
- It can be semi-automatic or manual inspection of analog multi meter, clamp type current meter, all kinds of electric meter, (voltmeter, ammeter, frequency meters, resistance meter) basic error
- The equipment can be generated with 2-31 harmonic wave, harmonic number, order, amplitude and harmonic phase of fundamental wave can be programmed
- Power amplifier working frequency range is 40Hz-1KHZ, has a good linear. Current amplifier is constant current source; voltage amplifier is constant voltage source. Because of light weight, this device is more suitable for field use
- With RS-232 interface, this device is controlled by PC through the PC software (optional), can be automatic or manual inspection, and the results are processing and management
- Has a non-volatile memory, it can store 500 pieces of the raw data of tested meter, for access and upload
PARAMETERS
| Electrical parameters | ||
|---|---|---|
| Power supply | Single phase AC 220V±10% or 110V±10%, 50/60HzAC | |
| AC Voltage output | ||
| range | 200mV, 400mV, 2000mV, 4000mV, 20V, 100V, 200V, 500V, 1000V |
|
| Range 20V-1000V | Accuracy | ±(0.03%RD+0.02%FS) |
| Stability | ≤0.01% FS /60s | |
| Range 200mV-4000mV | Accuracy | ±(0.3%RD+0.2%FS) |
| Stability | ≤0.04% FS /60s | |
| Load capacity | 20VA | |
| Waveform distortion | ≤0.3% | |
| Adjustable Range | 0-120% FS (1000V not included) | |
| Fineness | 5×10-5 | |
| AC Current Output | ||
| Range | 2mA, 4mA, 20mA, 40mA, 0.2A, 0.5A, 2A, 5A, 10A, 20A | |
| Range 0.2A-20A | Accuracy | ±(0.03%RD+0.02%FS) |
| Stability | ≤0.01% FS /60s | |
| Range 2mA-40mA | Accuracy | ±(0.3%RD+0.2%FS) |
| Stability | ≤0.04% FS /60s | |
| Load capacity | 20VA | |
| Waveform distortion | ≤0.3% | |
| Adjustable Range | 0-120% FS | |
| Fineness | 5×10-5 | |
| Frequency Output | ||
| Range | 45-65Hz | |
| Fineness | 0.001Hz | |
| Accuracy | 0.01Hz | |
| Harmonic Wave | ||
| Times | 2-31 | |
| Extent | 0-20% | |
| Each harmonic phase fineness | 0.01·N (N is harmonic order) | |
| DC voltage output | ||
| Range | 200mV, 400mV, 2000mV, 4000mV, 20V, 40V, 100V, 200V, 400V, 1000V |
|
| Load capacity | 20W | |
| Adjustable range | 0-110% FS (1000V not included) | |
| Adjustable fineness | 5×10-5 | |
| Stability | ≤0.01% FS /60s (peak-peak value) | |
| Accuracy | ±(0.03%RD+0.02%FS) | |
| Ripple wave | ≤1% FS | |
| DC current output | ||
| Range | 20uA, 40uA, 200uA, 400uA, 2mA, 4mA, 20mA, 40mA, 0.2A, 1A, 2.5A, 5A, 10A, 20A |
|
| Load capacity | 20W | |
| Adjustable Range | 0-110% FS (1000V not included) | |
| Adjustable Fineness | 5×10-5 | |
| Stability | ≤0.01% FS /60s (peak-peak value) | |
| Accuracy | ±(0.06%RD+0.04%FS) | |
| Ripple wave | ≤1% FS | |
| Resistance box | ||
| Range | 0-200Ω, 200-400Ω, 0-2kΩ, 2kΩ-4kΩ, 0-20kΩ, 20kΩ-40kΩ, 0-200kΩ, 200kΩ-400kΩ, 0-2MΩ, 2MΩ-4MΩ |
|
| Fineness | 0.02% | |
| Range 0-2kΩ, 0-20kΩ, 0-200kΩ | ||
| Range 0-2kΩ | Adjustable Range | 0-100%FS |
| Accuracy | ±(0.12%RD+0.08%FS) | |
| Range 0-200Ω,0-2MΩ | Adjustable Range | 0-100% FS |
| Accuracy | ±(0.3%RD+0.2%FS) | |
| Range 2kΩ-4kΩ, 20kΩ-40kΩ, 200kΩ-400kΩ | ||
| Range 2kΩ-4kΩ | Adjustable Range | 5%-100%FS |
| Accuracy | ±(0.12%RD+0.08%FS) | |
| Range 200-400Ω, 2MΩ-4MΩ |
Adjustable Range | 5%-100% FS |
| Accuracy | ±(0.3%RD+0.2%FS) | |
| Clamp meter range | ||
| 200A | Accuracy | ±0.2% |
| 600A | Accuracy | ±0.5% |
| 1000A | Accuracy | ±1% |
| Dot frequency square wave output | ||
| Range | 1kHz, 5kHz, 10kHz, 50kHz, 100kHz, 200kHz, 1000kHz | |
| Square wave amplitude | 4.5V | |
| Setting accuracy | 5×10-5 | |
| Mechanical parameters | ||
| Dimension (L×W×H) (mm) | 440x360x160 | |
| Weight (kg) | 12 | |
| Environmental conditions | ||
| Operating temperature | 20°C±10°C | |
| Relative humidity | ≤85%RH | |
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.