Product Description

Kwh Mono Phase Portable Meter Calibration Onsite Tester,Self-Supply Power ,Wide Mearsurement Range,High Definition,

 

 

INTRODUCTION

The GF1021 portable test system consists of an integrated single-phase current source and a single-phase electronic reference standard of accuracy class 0.05. Characteristic features of the GF1021 are its wide measuring range, high accuracy and high tolerance to unwanted external influences. The CheckSystem 2.1 S allows the monitoring of meter installations as well as analysis of the local mains conditions.

 

FEATURES

  • Accuracy class 0.05
  • 0-120A, 0-500V
  • Test 3pcs or 2pcs meter synchronously
  • Start testing and creep testing
  • Reference standard and power source integrated
  • Test by automatic or manual
  • 7 inch TFT touch screen
  • Weight light 8Kg
  • Recorder 500 sets energy meter data
  • Overload, short circuit, open circuit protection

PARAMETERS

Accuracy class 0.05%, 0.1%
Power supply One Phase AC 85-265V, frequency 50/60Hz.
AC Voltage output 
Range 57.7V, 100V, 220V, 380V; max 500V
Adjustment range (0-120)%RG(1)
Adjustment fineness 0.01%RG, 0.1%RG, 1%RG, 10%RG as optional.
Stability 0.01%/120s
Distortion 0.1% (Non-capacitive load)
Output load max 30VA
Measuring accuracy 0.05%RG
AC Current output 
Range 200mA, 1A, 5A, 20A, 100A; max 120A
Adjustment range (0-120)%RG
Adjustment fineness 0.01%RG, 0.1%RG, 1%RG, 10%RG as optional.
Stability <0.01%/120s
Distortion ≤0.1% (Non-capacitive load)
Output load max 50VA
Accuracy 0.05%RG
Power output 
Active power output stability <0.01%RG/120s
Reactive power output stability <0.02%RG/120s
Active power measuring accuracy 0.05%RG
Reactive power measuring accuracy 0.1%RG
Phase Output
Output adjustment range 0°-359.99°
Output adjustment fineness 10, 1, 0.1, 0.01 as optional.
Resolution 0.01°
Accuracy 0.03°
Power factor
Adjusting range -1 ~ 0 ~ 1
Resolution 0.0001
Measurement accuracy 0.0005
Frequency Output
Adjustment range 40Hz-70Hz
Output adjustment fineness 5Hz, 1Hz, 0.1Hz, 0.01Hz as optional.
Resolution 0.001Hz
Accuracy 0.005Hz
Voltage /Current/Harmonic Setting
Harmonic number 2-51times
Harmonic content 0-40%
Harmonic phase 0-359.99
Harmonic setting accuracy (10%±0.1%)RD(2)
Power Energy Measurement Error
Active power energy 0.05%RG
Reactive power energy 0.1%RG
Power Pulse Output
Power pulse type active pulse, reactive pulse
Active power pulse output 5V,10mA
Power Pulse Input
Energy pulse type support active and reactive pulse, the highest frequency power
pulse input is 180K.
Mechanical parameters
Dimensions (W×D×H) (mm) 325×275×135
Weight (kg) 8
Environmental conditions
Ambient temperature -10°C to +50°C
Relative humidity 35%-85%

 

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
Location Oriental HuaRui A, No. 150 Guanzhuang Road, Chaoyang District, Beijing, 100024, China
Contact Person Andy

Request A Quote

Please check your email address.
Your message must be at least 20 characters.