Three Phase 24V OLTC Transformer Test Instruments

Price Negotiable
Price: Negotiable
MOQ: 1Set
Delivery Time: 3-20 work day
Brand: GDZX
Product Description

Transformer Testing Equipment

Three Phase 24V Transformer On Load Tap Changer Tester 

This tester is mainly used to measure the transformer on-load tap-changer transition waveform, transition time, the instantaneous transition resistance, three-phase synchronization and so on.

 

 

The instrument features highly intelligent, English menu prompts, simple operation. Instrument small size, light weight, strong anti-interference ability.

It is ideal instrument to ensure safe production and good quality in power plants units, transformer manufacturing industry.     

 

 

Features
1.  Large output current, light weight.
2.  Open circuit voltage 28V, 1A gear for testing 10Ω transition resistance, 0.5A, 0.3A for larger transition resistance.
3.  Perfect protection circuit, reliable to use.
4.  Vertical chassis structure, 5.7-inch large LCD display, easy site operation.
5.  U disk storage function
 
 
Technical Indicators

 

1. Output current: 1.0A, 0.5A, 0.3A gears

2. Resistance range: 1.0A: 0.1 ~ 10Ω; 0.5A: 5 ~ 20Ω; 0.3A: 10 ~ 40Ω.

3. Resistance measurement accuracy: ± (reading × 5% + 5 words), resolution: 0.01Ω.

4. Transition time measurement range: 1 ~ 250mS.

5. Transition time measurement accuracy: ± 1mS, resolution: 0.1mS.

6. Sampling frequency: 10K.

7. Storage: U disk storage, local storage.

8. Operating temperature: -20 ℃ ~ +50 ℃.

9. Environmental humidity: ≤ 90% RH, no condensation.

10. Working power: AC220V ± 10%, 50Hz ± 10%

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Wuhan GDZX Power Equipment Co., Ltd
Location No.1 Fenghuangyuan Second Road, Jiangxia District, Wuhan City, Hubei Province, China
Contact Person Annie

Request A Quote

Please check your email address.
Your message must be at least 20 characters.