High Vacuum Transformer Oil Purifier for Power Transformer Maintenance
VFD Series of signal and double stage high-efficient vacuum oil purifier is to remove free and dissolved water, gases, and mechanical impurities from insulating oils so as to ensure its purity and improve its insulation property. It is suitable for the application to oil treatment 500KV super-voltage transforming equipment and 220KV transformers. It is also suitable for the treatment of capacitor oil, transformer oil and freezer oil.
- VF series - Single-Stage Vacuum Transformer oil purifier machine
- VFD series - Double-Stage Vacuum Insulation Oil Filtration Machine
- VFD-R series - Double-Stage Vacuum Black Insulation Oil Regeneration Filtration Machine
- Doubles the evaporation area by adopting Huazheng horizontal double vacuum separation technology efficiently and reliability thorough removal of gas in the oil by using coalescing oil spray separator
- Adoption of American fine filter element, fineness: 5μm, ß≥1000
- Low noise and long life of the oil transport system
- Adoption of American heating technique with the way of thermal radiation, constant temperature control
- The use of float valve and photoelectric oil level control, eliminates supervision
- Adoption of French de-foaming technique to avoid oil leaking
- Controlled digitally and automatically by PLC
- Major electric apparatus are imported from America, so the controlling system safe and reliabl
Item Before After Water Content 50-100ppm ≤4ppm Gas Content High ≤0.1% Particle Size >25μm ≤5μm Breakdown Voltage 35-45kV ≥75kV
- Normal appearance type, shelf-covering type and explosion-proof type. For last the lifetime of the machine
- Fixing type, mobile type with four wheels and mobile type with trailer. You can use is at every place as you need
- The color can be customized as you required
| Item | Unit | VFD-30 | VFD-50 | VFD-80 | VFD-100 | VFD-150 | VFD-200 | VFD-300 |
|---|---|---|---|---|---|---|---|---|
| Flow Rate | L/H | 1800 | 3000 | 4800 | 6000 | 9000 | 12000 | 18000 |
| Vacuum Range | Mpa | -0.092 ~ -0.099 | ||||||
| Working Pressure | Mpa | ≤0.2 | ||||||
| Max Vacuum Range | Pa | ≤50 | ||||||
| Temperature Range | ℃ | 45 ~ 65 | ||||||
| Breakdown Voltage | Kv | ≥75 | ||||||
| Impurity Size | μm | ≤5 | ||||||
| Dielectric Loss | Tg | ≤0.005 | ||||||
| Interfacial Tension | mn/m | ≥40 | ||||||
| Water Content | PPM | ≤4 | ||||||
| Gas Content | % | ≤0.1 | ||||||
| Power Supply | 380V/3P/50Hz(or as needed) | |||||||
| Working Noise | dB(A) | ≤72 | ≤72 | ≤72 | ≤72 | ≤78 | ≤78 | ≤78 |
| Heating Power | Kw | 30 | 48 | 72 | 90 | 120 | 180 | 240 |
| Total Power | Kw | 35 | 54 | 77 | 98 | 129 | 189 | 254 |
| Pipeline Diameter | mm | DN25 | DN32 | DN32 | DN40 | DN50 | DN65 | DN65 |
| Net Weight | Kg | 550 | 850 | 1000 | 1100 | 1400 | 1600 | 2200 |
| Size | length (mm) | 1500 | 1500 | 1700 | 1900 | 2100 | 2100 | 2600 |
| width (mm) | 1200 | 1200 | 1500 | 1400 | 1550 | 1550 | 1800 | |
| high (mm) | 1750 | 1750 | 1850 | 1800 | 1900 | 1900 | 2000 | |
- TF series oil purifier: Turbine oil purifier system is particularly suitable for purifying turbine lubricating oil. It also applies to treat hydraulic, coolant oil and other lubrication in which contain large of water, vapor, impurities, sludge, dielectric and colloid.
- LV series oil purifier: Lubrication Oil Filter System are suitable especially for purifying and restoring hydraulic oil, machine oil, coolant oil and various other lubrication oil.
- GER series oil purifier: Used oil regeneration system is suitable to regenerate used internal-combustion engine oil including diesel engine oil, gasoline engine oil, and used hydraulic oil, other used lubrication oil of machinery.
- GED series oil purifier: it is used to recycle all kinds of waste oil into base oil or diesel oil with high quality.
Yes.
Yes, optional online filtration available.
11kV to 1000kV.
Depends on oil condition and flow rate.
ISO, CE.
220V, 380V, 415V, 440V, 460V available.
Contaminated transformer oil can cause:
- Reduced dielectric strength
- Internal arcing
- Transformer overheating
- Insulation aging
- Unexpected power outages
Regular oil purification helps:
- Extend transformer life
- Reduce maintenance costs
- Improve electrical reliability
- Avoid transformer replacement
Location:
Transformer Capacity: 50MVA
Problem:
- Water contamination
- Low dielectric strength
Result:
- Moisture reduced to 3ppm
- Breakdown voltage increased from 42kV to 78kV
- Transformer returned to service

Get in Touch