300V Automatic Energy Meter Calibration Equipment Three Phase Accuracy 0.05 120A
Automatic Energy Meter Calibration Equipment high accuracy 0.05 120A 300V three phase
KE8302M Automatic Energy Meter Calibration Equipment
Accuracy : 0.05 , Used for the test of three phase CT/PT meter with a accuracy class below 0.2, and can also test single phase meter if adding an isolation voltage transformer.
Main features:
- Forward and reverse active energy / forward and reverse reactive energy error test
- Creeping and starting test
- Standard deviation, 24 hour variation test
- Timing error test
- Influencing quantity test of voltage, frequency, harmonic
- Calibration and verification of constant
- Auto protection of short circuit of voltage, open circuit of current, and overload.
- Test of neutral current (optional)
- Auto mark locking increases the efficiency of test
- Full automatic, semi automatic and manual operation available
- Adopt multi-serial port system, realizing the parallel communication of computer and the tested meters( optional)
- Test of tilt impact (optional)
- Register indicating value, register combination error test
- Powerful computer management system, easy and user-friendly
- Perfect database management makes the storage, searching, and viewing of the data possible, and the data can be converted and exported in other forms
Main Specification:
Output voltage
Limit: 57.7V / 100V / 220V / 380V
Adjustment range: 0~120%Un
Adjustment fineness: rough adjustment 10%;
intermediate adjustment 1%;
fine adjustment 0.1%;
Wave distortion: ≤0.3%
Phase shift influence: <0.1%
Load variance ratio: ≤±0.3% full rate value (pure resistance, sensibility, compatibility)
Accuracy rate of the monitor: 0.3% (or 0.03%) ±2 characters
Output current
Limit: 0.025A -- 120A, automatic grade seeking
Adjustment range: 0 -- 120%In
Adjustment fineness: rough adjustment 10%;
intermediate adjustment 1%;
fine adjustment 0.1%;
Wave distortion: ≤0.3%
Phase shift influence: <0.1%
Load variance ratio: ≤±0.3% full degree value (pure resistance, sensibility)
Accuracy rate of the monitor: 0.3% (or 0.03%) ±2 characters
Output phase
Adjustment range: 0.01°-- 360°
Adjustment fineness: rough adjustment 10°;
intermediate adjustment 1°;
fine adjustment 0.1°;
micro adjustment ≤0.01°
Load variance ratio: <±0.3°
Accuracy rate of the monitor: 0.3°±1 character
Output frequency
Adjustment range: 45.000Hz -- 65.000Hz
Adjustment fineness: rough adjustment 1Hz;
intermediate adjustment 0.1Hz;
fine adjustment 0.01Hz;
Load variance ratio: <±0.5%
Accuracy rate of the monitor: 0.01Hz
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.