Indoor Metal Clad And Metal Enclosed Switchgear For Electric Power Distribution
Electric Power Distribution Equipment KYN28-12kv Indoor Switchgear/Switchboard/ Switch Effective Interlocking Cabinet
Electric Power Distribution Equipment KYN28-12kv Indoor Switchgear/Switchboard/ Switch Effective Interlocking Cabinet is suitable for 3- phase AC 50Hz/3.6~12kV single busbar and single busbar section system. Apply to distribute electricity power and implement system control,protection,supervision monitoring.The switchgear comply with the standards IEC62271,GB3906,DL404.
Operating conditions
- Ambient temperature:max. to +40℃min. to-10℃.
- Altitude: 1000m(max).
- Relative humidity: daily average less than 95% ,monthly less than 90%.
- Shock of earthquake: less than 8 magnitude.
- This product should not be used under conditions of fire, explosion, earthquake and chemical corrosion environments.
Note: Special condition and requirement, consult with the manufacturer.
Features of KYN28-12 System
- Metal-cald and partition completely,efectively prevent faults spreading.
- The low voltage section is completely separated from the high voltage sections.
- Enclosure p rotection deg ree is IP4X, protect against electric shock and ing ress of solid foreign bodies.
- Simple but effective interlocking prevents maloperation.
- Space is provided for multiple cable connections,Installation and maintenance is convenient.
- Withd rawble part of the same design are mutually interchangeable,an exchange of VCB is very simple.
The technica data
| Name | Unit | Data |
| Rated voltage | KV | 3.6/7.2/12 |
| Rated power-frequency withstand voltage(1min.) | KV | 18/23/42 |
| Rated lightning impulse withstand voltage | KV | 40/60/75 |
| Rated frequency | Hz | 50 |
| Main busbar rated current | A | 2500/3150/4000 |
| Branchal busbar rated current | A | 2500/3150/4000 |
| Rated short-time withstand current(rms),4S | KA | 16/20/25/31.5/40/50 |
| Rated peak withstand current | KA | 40/50/63/80/100/125 |
| Enclosure protection level | IP4X |
Note:
1.Enforced cooling is necessary when the current is over and including 31 50A of VCB.
2.The the rmaI stability of cu rrent transformer and cu rrent design and stability,in order to confi rm the specific.
Outline dimension&weight
| Height | 2300mm | |
| Width | Rated current 1600A and below | 800.(650*)mm |
| Rated current 2000A and above | 1000mm | |
| Depth | Front maintenance | 1350 |
| Double-face maintenance | 1500/1660mm | |
| Weight | 800-1200kg | |
The above dimensions are suitable for breaker VD4.
Construction
The basic structure of the switchgear panel is comprised with the panle itself and drawable part.
The panel is assembled by bolts,the anti-corrosion steel plate is used for the shell and internal partitions.And the panel is consisted by four separated compartments,which is truck compartment,busbar compartment,cable compartment,low-voltage compartment.
There are two kinds of maintenances for this kind of switchgears,one is called front maintenance type,the other is called double-face maintenance type.And the drawable units can be divided into the following units according to its own functions.
- VCB truck
- PT truck
- Disconnect truck
- Metering truck
- HV fuse truck
- Lightning arrester truck etc.