Differential Pressure Deltabar PMD75

Price Negotiable
Price: Negotiable
MOQ: 1PCS
Delivery Time: 5-8 work days
Product Description

Differential pressure Deltabar PMD75

 

Field of application

 

The Deltabar PMD75 differential pressure transmitter with piezoresistive sensor and welded metallic membrane is used in all industries for continuous measurement in liquids, vapors and gases. The 3-key operation enables simple and reliable commissioning and operation. The integrated HistoROM data module allows easy management of process and device parameters. Designed according to IEC 61508 for use in SIL2/3 safety applications.

 

For level, volume or mass measurement in liquids, differential pressure monitoring as well as flow measurement (volume or mass flow) in conjunction with primary elements in gases, vapors and liquids.

 

Process connections: Threads

Process temperature: -40 to 85°C (-40 to 185°)

Measuring ranges: 0.25mbar to 40bar (0.0036 to 600psi)

Accuracy: ±0.05%, "Platinum" ±0.035% (optional)

International explosion protection certificates, overfill prevention WHG, SIL, hygienic approvals, marine approvals

 

 

Benefits

  • Best accuracy, reproducibility and long-term stability
  • Highest safety due to gas tight feedthrough with capabilities up to SIL2/3, certified to IEC 61508
  • Easy menu-guided commissioning via local display, 4 to 20mA with HART, PROFIBUS PA, FOUNDATION Fieldbus
  • HistoROM data management concept for fast and easy commissioning, maintenance and diagnostics
  • Cost savings with modular concept for easy replacement of sensor, display or electronics
  • Overload-resistant up to 420bar / 42MPa / 6300psi, function-monitored
  • Seamless and independent system integration (HART/PA/FF)

Product Description

Measuring principle Differential pressure
Characteristic Digital transmitter with metallic measuring diaphragms
Modular transmitter
Long-term stability
High static pressure/Overload resistance
Secondary process barrier
Supply voltage 4...20 mA HART
10,5...45V DC (Non Ex):
Ex ia: 10,5...30V DC
PROFIBUS PA:
9...32 V DC (Non Ex)
FOUNDATION Fieldbus:
9...32 V DC (Non Ex)
Reference Accuracy Standard: 0.05%
Platinum: up to 0.035%
Long term stability 0.03 % of URL/ year
0.05 % of URL/ 5 years
0.08 % of URL/ 10 years
Process temperature -40°C...85°C(-40°F...185°F)
Ambient temperature -50°C...85°C(-58°F...185°F)
Measuring cell 10 mbar...250 bar
(0.15 psi...3750 psi)
Smallest calibratable span 1 mbar (0.015 psi)
Vacuum resistance 50 mbar (0.73 psi)
Max. Turn down 100:1
Max. overpressure limit On one side:
420 bar
(6300psi)
Process connection 1/4-18NPT
RC1/4"
Material process membrane 316L, AlloyC,
Tantal,
Gold-Rhodium
Material gasket Viton, PTFE, EPDM, NBR
Fill fluid Silicone oil
Inert oil
Communication 4...20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
Safety approvals SIL
Design approvals NACE MR0103
EN10204-3.1
Certificates / Approvals ATEX, FM, CSA, CSA C/US, IEC Ex, INMETRO, NEPSI, EAC, UK Ex
Specialities Diagnostic functions
Material housing 316L, Die-cast aluminum
Marine approvals GL/ ABS
Successor PMD75B

 

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Xi'an Kacise Optronics Co.,Ltd.
Location 2nd Building, Tianyuan International Mansion, High-tech Zone, Xi'an City, Shaanxi Province, China
Contact Person Evelyn Wang

Request A Quote

Please check your email address.
Your message must be at least 20 characters.