Dwyer MSX Pro Pressure Transmitter (Model: MSX-20W-PA)

Price Negotiable
Price: Negotiable
MOQ: 1PCS
Delivery Time: 5-8 work days
Brand: Dwyer
Product Description
Dwyer MSX Pro Pressure Transmitter (Model: MSX-20W-PA)
Key Specifications
Attribute Value
Pressure Type Pressure Transmitter
Model MSX-20W-PA
Accuracy ±1% FSO
Temperature Limits -4 to 158°F (-20 to 70°C)
Output Signals 4-20 mA
Adjustments Digital Push-button
Product Overview

The Dwyer MSX Pro Pressure Transmitter (MSX-20W-PA) is a versatile Magnesense differential pressure sensor designed for building control applications, monitoring differential pressure, air velocity, and volumetric flow. Built on the stability of the MS2 Magnesense II series, it simplifies configuration with 32 selectable pressure ranges (Pa, mm w.c., in w.c.) in unidirectional/bidirectional modes.

Dwyer MSX Pro Pressure Transmitter front view showing LCD display Dwyer MSX Pro Pressure Transmitter side view showing electrical connections
Key Features
Precision Measurement

Monitors differential pressure, air velocity, and volumetric flow in building systems with ±1% FSO accuracy across 32 pressure ranges (Pa, mm w.c., in w.c.).

Configurable Output Modes

Linear pressure output or velocity output with square root extraction for flow calculation. Dual signals: 4-20 mA (2-wire) and selectable 0-10 V/0-5 V (3-wire) for control and signal verification.

Flexible Installation

10-36 VDC (2-wire) or 17-36 VDC/21.6-33 VAC (3-wire) power input. Features 1/2" NPS thread electrical entry and orientation-independent mounting.

User-Friendly Interface

4-digit LCD with 180° rotatable display for optimal visibility in any installation. Optional toolless terminal block for quick wiring.

Safety & Environmental Ratings

UL94 V-0 fire rating and plenum-rated materials for hazardous environments. Pressure limits: Up to 3.6 psi (operation) and 6 psi (burst) for select ranges.

Application Versatility

Ideal for filter monitoring, clean room pressure control, duct static pressure, and VAV system airflow.

Technical Specifications
Parameter Specification
Service Air and non-combustible, compatible gases
Accuracy ±1% FSO
Power Requirements 10-36 VDC (2-wire), 17-36 VDC or isolated 21.6-33 VAC (3-wire)
Output Signals 4-20 mA (2-wire); 0-10 V or 0-5 V selectable (3-wire)
Electrical Entry 1/2" NPS thread
Display 4 digit LCD
Mounting Orientation Pressure sensor measurement unaffected by orientation

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Xi'an Kacise Optronics Co.,Ltd.
Location 2nd Building, Tianyuan International Mansion, High-tech Zone, Xi'an City, Shaanxi Province, China
Contact Person Evelyn Wang

Request A Quote

Please check your email address.
Your message must be at least 20 characters.