Chinese Globe Valve Body Control Valve AUMA SA SAR Multi-turn Electric Control Valve Actuators
AUMA's SA 07.1 – SA 16.1 and SAR 07.1 – SAR 16.1 are multi-turn electric actuators designed for automating industrial valves, particularly gate and globe valves requiring full revolutions. The SA series is optimized for open-close duty (short-time S2), while SAR supports modulating duty (intermittent S4/S5). In the AUMA NORM version (without integral controls), they are driven by a 3-phase AC motor, featuring self-locking worm gearing to withstand thrust and transmit torque. These actuators include manual handwheel operation for emergencies and are built for reliable performance in harsh environments, with options for explosion-proof applications in dust zone 22. They comply with EN ISO 5210 standards and are certified under EC Directives for machinery, EMC, and low voltage.
- Versatile Duty Types: SA for short-time open-close (S2 - 15/30 min), SAR for intermittent modulating (S4 - 25/50%, S5 - 25%) with up to 1,500 starts per hour.
- Torque and Limit Control: Adjustable torque switching for OPEN/CLOSE directions; limit switching with single, tandem, or triple switches (galvanically isolated options).
- Manual Operation: Lockable handwheel that does not rotate during motor operation; engages/disengages easily for emergency use.
- Feedback Options: Analogue position/torque signals (0/4-20 mA via RWG); mechanical position indicator; running indication via blinker.
- Protection Mechanisms: Motor thermoswitches or PTC thermistors; overload protection; automatic phase correction for 3-phase supply.
- Environmental Resilience: IP67/IP68 enclosure (submersion up to 8m/96 hours); vibration resistance 2g (10-200 Hz); KS/KX corrosion protection for moderate/extreme pollutants.
- Assembly Flexibility: Various output drives (A, B1-B4, E) per EN ISO 5210/DIN 3210; stem nut machining for custom fits; accessories like stem protection tubes.
| Parameter | Details |
|---|---|
| Type of Duty | SA: S2 - 15/30 min; SAR: S4 - 25/50%, S5 - 25% |
| Torque Range | Refer to name plate (adjustable tripping) |
| Output Speed | Refer to name plate |
| Turns per Stroke | 1-500 (standard); up to 5,000 (option) |
| Motor | 3-phase AC asynchronous, IM B9, insulation F/H |
| Power Supply | Nominal voltages/frequencies per name plate; ±10/30% voltage tolerance, ±5% frequency |
| Motor Protection | Thermoswitches (NC) or PTC thermistors |
| Self-Locking | Yes for speeds up to 90 rpm (50 Hz)/108 rpm (60 Hz) |
| Limit Switching | Single (1 NC/NO), tandem (2 NC/NO isolated), triple (3 NC/NO isolated); DUO for intermediates |
| Torque Switching | Single/tandem switches (isolated option); adjustable OPEN/CLOSE |
| Feedback | Potentiometer or RWG (0/4-20 mA); Mechanical indicator; Blinker running signal |
| Heater Power | 12.5-25 W (110-400 V AC) |
| Manual Operation | Handwheel, lockable option |
| Electrical Connection | AUMA plug/socket (screw-type); Options: terminals/crimp |
| Valve Attachment | B1 (EN ISO 5210 standard); Options: A, B2-B4, E, AF, etc. |
| Lifetime | Open-close: 15,000-20,000 cycles; Modulating: 3.5-5 million steps |
| Ambient Temperature | -40°C to +80°C (open-close), +60°C (modulating) |
| Enclosure Protection | IP67/IP68 |
| Vibration Resistance | 2g, 10-200 Hz |
| Corrosion Protection | KS (standard); KX/KX-G (options) |
| Installation Altitude | ≤2,000 m (higher on request) |
| EU Compliance | Machinery (2006/42/EC), EMC (2004/108/EC), Low Voltage (2006/95/EC) |
Suitable for industrial valves in water/power plants, wastewater treatment, and chemical industries. SA for open-close duties in pipelines/tanks; SAR for modulating flow/pressure control. Approved for Ex zone 22 dust areas (option); indoor/outdoor use with low to high pollutant concentrations. Not for continuous operation, buried service, permanent submersion, or gas explosive zones (use Ex variants).
- What is the difference between SA and SAR? SA is for open-close (short-time duty), SAR for modulating (intermittent duty with higher starts).
- How to set torque switching? Open switch compartment, adjust dials for OPEN/CLOSE; refer to page 24 in manual.
- Can it handle wrong phase sequence? Yes, automatic correction for 3-phase AC supply.
- What if fault during commissioning? Check rotation direction (page 27), limit switching (page 28), or motor protection tripping (page 32).
- How to store? Dry, well-ventilated; max 2 years; refer to page 8.
Phone/WeChat/WhatsApp:
+8613916209596
Email: svetama@gbsxj.com
- AUMATIC AC 01.2: Integral actuator controls with fieldbus.
- SQ/SQR Part-Turn Actuators: For butterfly/ball valves.
- GK/GST Gearboxes: For higher torque with SA/SAR.
- AM 01.1 Controls: Basic modular version.
- AUMA CDT Software: For diagnostics via Bluetooth.
Get in Touch