MNS Low Voltage Electrical Distribution Box Drawer - Out Switchgear Commercial Industrial
MNS Low Voltage Drawer-out Type Switchgear up to 4,000A for Commercial and Industrial Electrical Distribution IEC 61439
MNS Drawer Type Low-voltage Switchboard
MNS system are suitable for applications in all fields concerning the generation, distribution and use of electrical energy, e. g., they can be used as: Main and sub-distribution boards for energy and Motor current supply of Motor Control Centers
• Utility companies
• Power plants
• Oil refineries
• Off-shore drilling platforms
• Production facilities
• Buildings for other than dwelling purposes.
The MNS system is full complied with GB7251.1, IEC 439-1, EN 60 439-1, VDE 0660 part 500, BS 5486 Part 1 and UTE 63-410
MNS switchgear assembly is of scalable design, enabling ABB to supply integrated solutions for today's challenging business environment. It is the leading technology combining maintenance-free frame structures and busbars, a fully modular construction and the capability to integrate feeder, motor starter, variable speed drives, power factor compensation etc. and even UPS technologies in safety focused, space saving and project-optimized manner.
Main benefits
-
Unmatched safety for protection of personnel and plant exceeding standard requirements
-
Reduced operational expenditure through maintenance free bus bar design
-
Increased availability through modular design using withdrawable, plug-in, compact or fixed functional units
-
Reliable, flexible and scalable fully accessible from the front
-
Space saving design with compact, back-to-back or duplex arrangement
Main features
-
Fully certified to IEC 61439-1/-2 low-voltage switchgear assembly up to 690V, up to 6300A, up to 100kA
-
Passive arc protection criteria 1 to 7, tested acc. IEC TR 61641 Ed.3 criteria 1 to 7, arc proof certified up to 690V, 100kA
-
Modular construction, extendable at both ends and reconfiguration capabilities
-
Ease of operation with closed doors and single handle operation
-
Segregation up to form 4b
Main technical data
|
No. |
Item |
Unit |
data |
||
|
1 |
Rated voltage |
V |
Up to 690 |
||
|
2 |
Rated current for system |
A |
4000(special to 6300A) |
||
|
3 |
Rated current for busbar |
Horizontal Busbar |
A |
Busbar 6300 *extremely* |
|
|
1600 @+40ºC |
|||||
|
Vertical Busbar |
|||||
|
4 |
Rated frequency |
HZ |
2000*Note* |
||
|
5 |
Power frequency with voltage 1min |
kV |
8 |
||
|
6 |
Rated Short-timeWithstand Current |
Horizontal Busbar |
kA/1S |
55-100/105-250 |
|
|
60/130-150 |
|||||
|
Vertical Busbar |
|||||
|
7 |
Over voltage class |
III |
|||
|
8 |
Pollution Degree |
3 |
|||
|
9 |
Protection Degree |
IP30/IP40/IP54 |
|||
|
10 |
Outline Dimensions(H*W*D) |
mm |
2200×600(800/1000)×600(800/1000) |
||
Note:
1. The current of vertical busbar is extremely up to 2000A@+35ºC,(+40ºC with cooler) .
2. Protection Degree of IP54 is taken into consideration for special design if needed.
Get in Touch