IPRU Surge Protection Device Low Voltage Components SPD 230V/400V Imax 10 20 40 65kA
Schneider Electric iPRU Surge Protection Device SPD 1,2,3,4 Pole 230V/400V Home or Industrial Use Imax=10,20,40,65kA
Characteristic
-
IEC test category: Class II test (8/20us)
-
Meet the standard: GB 18802.1-2011
-
Maximum sustainable operating voltage Uc : 350 V
-
Maximum discharge current Imax : 120/100/80/65/40/20/10 kA
-
Nominal discharge current In : 60/50/40/35/20/10/5 kA
-
Voltage protection level Up: 2.5/2.2/2.1/1.9/1.7/1.45/1.2 kV
-
Number of steps: 1P/2P/3P/4P/1P+N/3P+N
Advantage
-
Complete flow capacity level to meet different location installation requirements
-
Uc (LN) reaches 350V, Uc (L-PE) reaches 440V, and the work after accessing the system is safe and reliable.
-
The full range of 1P/2P/3P/4P pole products provides phase-to-phase and neutral-to-ground common-mode protection. The full range of 1P+N/3P+N poles provides phase-to-neutral and phase-to-phase Full-mode protection from neutral to ground, suitable for grounding systems such as TT and TN
-
GB 18802.1-2011 conformity assessment, CQC comprehensive certification
-
The cooperation relationship between SPD and backup protection circuit breaker has been fully verified by Shanghai Lightning Protection Center.
Application
-
Suitable for incoming line protection, secondary protection and tertiary protection, can be used in TN-C, TN-S, TT systems
|
Product Series |
IPRU |
|---|---|
|
product type |
Pluggable surge protector |
|
Product short name |
IPRU 20r |
|
Number of poles |
3P + N |
|
Output type |
Remote indication signal |
|
Surge protector application type |
Power distribution network |
|
Grounding system |
TT |
|
Surge protector test category |
(Type II) |
|---|---|
|
Structure principle and action characteristics of surge protector |
MOV |
|
Rated working voltage [Ue] |
230/400 V |
|
Maximum continuous operating voltage [Uc] |
Differential mode: 350 V (L - N ) |
|
Maximum [Up] voltage protection level |
Common mode <1.5 kV (N - PE) |
|
Local signal indication |
White/red mechanical indicator window |
|
Installation type |
Locking clip locking |
|
Installation method |
DIN rail mounting |
|
Width (multiple of 9mm) |
8 |
|
height |
85 mm |
|
width |
72 mm |
|
depth |
64 mm |
|
colour |
White (RAL 9003) |
|
Response time |
<= 25 ns |
|
Wiring ability |
Wiring or lower wiring on tunnel terminals 2.5...35 mm2 single strand hard wire |
|
Recommended cable |
4 mm2 fire (L) |
|
Tightening torque |
3.5 Nm |
|
standard |
GB 18802.1:2011 |
|---|---|
|
certified product |
CQC |
|
IP protection level |
Front panel: IP40 |
|
Operating temperature |
-25...60 °C |
|
Storage ambient temperature |
-40...70 °C |

Get in Touch