Suzhou Delfino Environmental Technology Co., Ltd.
                                                                                                           
Verified Supplier
11 Years
Since 2015
Menu

-10~+150℃ NTC10K/PT1000 Automatic Or Manual pH ORP Meter Controller For Water

Price Negotiable
Price: Negotiable
MOQ: Negotiable
Delivery Time: 7-10 work days
Brand: Daruifuno
Product Description

 

-10~+150℃ NTC10K/PT1000 automatic or manual pH ORP Meter Controller For Water

 

‍pH/ORP controller (also known as pH meter) equipment is suitable for the control of PH and ORP values in electroplating, metallurgy, textile, chemical and other wastewater, giving new life to the traditional chemical treatment method, fully realizing automatic monitoring, automatic medication, to ensure that the discharge of wastewater to meet the national discharge standards. 

 

Advantages of pH/ORP controller:

  • pH glass electrode measurement method
  • Two configurable SPST multifunction relays
  • With 1 high-precision 0/4-20mA current output
  • 3.2 inch LCD screen, rich content
  • Support multiple installation methods
  • AC and DC power modes, both wide voltage
  • Housing material reinforced ABS, protection class IP66

 
pH ORP controller Parameters:

Display Range pH: 0~14pH
ORP: -2000mV~2000mV
Temp.:-10~+150℃
Resolution pH: 0.01pH ORP: 1mV Temp.: 0.1℃
Accuracy ±0.02pH/±2mV
Temp. Compensation NTC10K/PT1000 automatic or manual
Relay Control Channel Quantity: 2
Control Type: main value control/temp. control/wash control
Contact Type: SPST
Contact Capacity: 3A 250V AC
Current Output Channel Quantity: 1
Output Type: active 4~20mA or 0~20mA
Max. Load: 1000Ω
Display Screen 3.2 inch graphic LCD display
Configuration information Power failure protection, parameters are retained indefinitely
Operating Environment 0~+60℃, relative humidity 0~95%, no condensation
Storage Environment -20~+70℃, relative humidity 0~55%, no condensation
Power Supply 100~240VAC or 18~36VDC, 3W Max
Installation Method Panel / wall / pipe mounting
Instrument Dimension 144*144*120 (unit: mm)
Protection Grade IP66
Instrument Weight About 800g


 

Probe Setting
 
Perform sensor calibration and view of sensor status.
After the probe is connected to the controller, it needs to be calibrated first due to the error between
the signal of the actual electrode and the standard.
 
pH Calibration
1. Preparation before calibration
  • In the menu “ select probe ”, select “ pH Glass probe ” or “ pH Antimony probe ”
  • pH 4.01, 6.86, 9.18 standard solution (1)
  • Deionized cleaning solution and absorbent paper
2. Zero Calibration
(1) Clean the probe with deionized cleaning solution, dry it with absorbent paper and put it
into pH 6.86 standard solution;
(2) After the measured value is stable, select “ 6.86pH CAL ” to start calibration;
3. Acid slope Calibration
(1) Clean the probe with deionized cleaning solution, dry it with absorbent paper and put it
into pH 4.01 standard solution;
(2) After the measured value is stable, select “ 4.01pH CAL ” to start calibration;
4. Alkali slope Calibration
(1) Clean the probe with deionized cleaning solution, dry it with absorbent paper and put it
into pH 9.18 standard solution;
(2) After the measured value is stable, select “ 9.18pH CAL ” to start calibration;
 
ORP Calibration
1. Preparation before calibration
  • In the menu “ select probe ”, select “ ORP probe ”
  • ORP 86mV, 256mV standard solution (1)
  •  Deionized cleaning solution and absorbent paper
2. Zero Calibration
(1) Clean the probe with deionized cleaning solution, dry it with absorbent paper and put it
into ORP 86mV standard solution ;
(2) After the measured value is stable, select " 86mV CAL " to start calibration;
3. Slope Calibration
(1) Clean the probe with deionized cleaning solution, dry it with absorbent paper and put it
into ORP 256mV standard solution;
(2) After the measured value is stable, select " 256mV CAL " to start calibration;
 

 


pH ORP controller Applications:

 

Acid and base (pH) regulation is to stabilize the PH value of the process medium in the required range to meet the needs of the process, in the electroplating process of electroplating bath pH control, metallurgical flotation process of pulp PH control, chemical process of the process medium mother liquor pH control. In the water treatment process, the pH value of the treated water will greatly affect the use effect of various chemicals, and different kinds of wastewater may not be allowed to discharge in the pH range after the completion of various treatments.

 

If you are interested in more product information about pH ORP controller APX2-C1, please contact us.


 
 
 

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Suzhou Delfino Environmental Technology Co., Ltd.
Location Room 301, Building 3, No. 25 Datong Road, High-tech Zone, Suzhou City, JIANGSU P.R CHINA
Contact Person Yuki Fu

Request A Quote

Please check your email address.