LW8-40.5 33KV 36KV sf6 circuit breaker priceer
Product Description
| LW8-40.5 33KV 36KV sf6 circuit breaker price |
|
![LW8-40.5 33KV 36KV sf6 circuit breaker price]()
Drawings
![LW8-40.5 33KV 36KV sf6 circuit breaker price]()
1. Environmental Condition
- Ambient temperature:-30℃~+40℃
- Altitude:≤3000m
- Wind pressure:≤700Pa
- Relative humidity:daily average relative humidity: ≤95%;monthly average relative humidity≤90;daily average saturated vapor pressure ≤2.2KPa;monthly average value ≤1.8KPa
- Air pollution level:Ⅲ
- Earthquake intensity:≤8 degree
- The installation should be free from fire, explosion, severe vibration, chemical corrosion and serious pollution
2. Technical Data
| No. |
Item |
Unit |
Data |
| 1 |
Rated voltage |
KV |
40.5 |
| 2 |
Rated current |
A |
2000 |
| 3 |
Rated frequency |
HZ |
50 |
| 5 |
Rated short circuit breaking current |
KA |
31.5 |
| 6 |
Rated short-circuit current (peak) |
KA |
50 |
| 7 |
Rated short-circuit withstand current |
KA |
20 |
| 10 |
Rated short circuit closing current(peak) |
KA |
50 |
| 13 |
Electrical life of rated short circuit breaking current |
times |
30 |
| 14 |
Rated short circuit duration |
s |
4 |
| 15 |
Rated line charging close current |
A |
31.5 |
| 16 |
Rated operation sequence |
|
O-0.3s-CO-180s-CO |
| 17 |
Split time |
ms |
≤60 |
| 18 |
Closing time |
ms |
≤100 |
| 19 |
Velocity of rigid composite |
m/s |
3.2 |
| 20 |
Velocity of rigidity |
m/s |
3.4 |
| 21 |
Mechanical life |
times |
6000 |
| 24 |
Quality of each circuit breaker |
kg |
1400 |
3. Application
Act as the protecting and controlling unit for grid equipments and industrial mining enterprises’ equipments, LW8-40.5 type outdoor SF6 circuit breaker is an outdoor device used in AC 50HZ three-phase 40.5KV power system. It is applicable to locations that need frequent operating in rated current or under repeatedly on/off short circuit current. Containing the current transformer for measurement and protection, it can directly replace SW2-35 less oil circuit breaker and various types of oil circuit breaker with transition bracket. It can also be used as a tie breaker and switching capacitor group situations with CT14 type spring mechanism.
4.Standards
- GB1984
- GB/T28001-2011 idt OHSAS18001:2007
- GB/T24001-2004 idt ISO14001:2004
5. Features
- Excellent breaking performance, short burning arc time, long life;
- Mechanical life of more than 3000 times;
- Operation frequently, each can be installed 12 current transformers;
- New type SF6 MKZ pointer type density meter, pressure gauge reading is not affected by temperature changes;
|