Long HV XLPE Cable Testing Device / Hv Test Equipment 3000KVA Or OEM Capacity
Variable Frequency Resonant Withstand Voltage Test Reactor For Long HV XLPE Cable
I. Application :
The high voltage test reactor is HV booster or generator in the variable frequency resonant withstand voltage circuit, it has large capacity and HV for one piece with higher Quality factor putput . it is special for the high voltage XLPE cable test with longer distance .
Fanke company can finish the design and produce the goods according to all kinds of customer's requirement . such as cylinder type and iron tank type .
Test reactor can be produced to be 130KV,150KV,155KV,200KV, 250KV, 300KV, 350KV, 400KV for each piece rated voltage according to different tested object scope or customer requried. The max. rated current of each HV reactor can be 1~5A,10A,15A,20A,25A,30A.
II. Test priciple figure:
VF: Variable Frequency Power Supply Source which is control and measurement part in the test circuit.
T : Excitation Transformer which provide the exciting voltage for HV test reactor
L : Test Reactor which is resonant inductance in the LC circuit and produce the test voltage
Cx: Tested Equipment
MOA1: Lightning Arrestor is protection part on the excitation transformer
C1,C2: Voltage divider(C1 is high voltage arm,C2 is low voltage arm ) which is HV voltage measurement part
III. General Technical data:
- Mode of system test: Series resonant with variable frequency
- System model : OEM
- Input power supply : 380±10%(three-phase),50Hz/60Hz
- Number of HV test reactor: OEM
- Rated output capacity: OEM
- Rated output Voltage: 150KV or OEM
- Max Test voltage : no more than 150KV,300KV,450KV
- Rated output current: 25A max or OEM
- Reg. Freq range : 20Hz-300Hz
- Output Resonance voltage waveform: sine wave
- THD of output waveform: ≤1%
- Insulation level: Under 1.1 times and keeping 1min, normal
- Duty cycle : 60mins on under rated current working condition ;
- Quality factor of test set itself: Q≥60
- Temperature rise: Less than 65K under rated current working 60mints;
- Noise level: No more than 65dB
- Reactor Structure: oil immersed type, epoxy tube cylinder type;
IV.Accessories
- Necessary corona rings
- Parallel cables of the reactor
- HV output cables(reactor to divide)
- Corona ring for test reactor
- A final test report, a quality Certificate ,a user manual and a packing list are offered .
V. Typical model of test reactors
1 Optional model for 132KV class XLPE cable on-site withstand voltage test
| Model | Rated voltage | Rated output current | Rated output capacity | Max Application |
| CHX-775KVA/155KV | 155KV | 5A | 775KVA | 132kV cable≤1km |
| CHX-1550KVA/155KV | 155KV | 10A | 1550KVA | 132kV cable≤2km |
| CHX-2325KVA/155KV | 155KV | 15A | 2325KVA | 132kV cable≤3km |
| CHX-3100KVA/155KV | 155KV | 20A | 3100KVA | 132kV cable≤4km |
| CHX-3875KVA/155KV | 155KV | 25A | 3875KVA | 132kV cable≤5km |
| CHX-7750KVA/155KV | 155KV | 50A | 7750KVA | 132kV cable≤10km |
| CHX-12400KVA/155KV | 155KV | 80A | 12400KVA | 132kV cable≤16km |
| CHX-15500KVA/155KV | 155KV | 100A | 15500KVA | 132kV cable≤20km |
| Special requirement can be made by order | ||||
Note :Tested cable voltage class≤ 132kV, 0.25uF/km
2 Optional model for 230KV class XLPE cable on-site withstand voltage test
| Model | Rated voltage | Rated output current | Rated output capacity | Max Application |
| CHX-2020KVA/255KV | 255KV | 8A | 2020KVA | 220~230kV cable≤1km |
| CHX-4080KVA/255KV | 255KV | 16A | 4080KVA | 220~230kV cable≤2km |
| CHX-6120KVA/255KV | 255KV | 24A | 6120KVA | 220~230kV cable≤3km |
| CHX--8160KVA/255KV | 255KV | 32A | 8160KVA | 220~230kV cable≤4km |
| CHX--10200KVA/255KV | 255KV | 40A | 10200KVA | 220~230kV cable≤5km |
| CHX--20400KVA/255KV | 255KV | 80A | 20400KVA | 220~230kV cable≤10km |
| CHX--25500KVA/255KV | 255KV | 100A | 25500KVA | 220~275kV cable≤12.5km |
| Special requirement can be made by order | ||||
Note :Tested cable voltage class≤ 230kV, 0.25uF/km
3 Optional model for 330KV class XLPE cable on-site withstand voltage test
| Model | Rated voltage | Rated output current | Rated output capacity | Max Application |
| CHX-3500KVA/350KV | 350KV | 10A | 3500KVA | 330kV cable≤1km |
| CHX-7000KVA/350KV | 350KV | 20A | 7000KVA | 330kV cable≤2km |
| CHX-10500KVA/350KV | 350KV | 30A | 10500KVA | 330kV cable≤3km |
| CHX-14000KVA/350KV | 350KV | 40A | 14000KVA | 330kV cable≤4km |
| CHX-21000KVA/350KV | 350KV | 60A | 21000KVA | 330kV cable≤5km |
| CHX-28000KVA/350KV | 350KV | 80A | 28000KVA | 330kV cable≤10km |
| Special requirement can be made by order | ||||
Note :Tested cable voltage class≤ 330kV, 0.25uF/km
4 Optional other model for long XLPE cable on-site withstand voltage test
| Model | Rated voltage | Rated output current | Rated output capacity |
Application (From 20Hz starting) |
| CHX-2600KVA/130KV | 130KV | 10A,20A | 1300KVA | For U0=64KV and below cable |
| CHX-3000KVA/150KV | 150KV | 10A, 20A | 3000KVA | For U0=87KV and below cable |
| CHX-10000KVA/250KV | 250KV | 20A, 40A | 10000KVA | For U0=127KV and below cable |
| CHX-20000KVA/250KV | 250KV | 20A, 80A | 20000KVA | For U0=127KV and below cable |
| CHX-21000KVA/350KV | 350KV | 20A, 60A | 21000KVA | For U0=230KV and below cable |
| CHX-42000KVA/350KV | 350KV | 20A, 80A | 42000KVA | For U0=230KV and below cable |
| Special requirement can be made by order | ||||
Note : XLPE cable test voltage is considering as 1.7U0
5 Optional model for HV or EHV class cable and GIS On-site AC hipot test
| Model | Rated voltage | Rated output current | Rated output capacity |
Application (From 20Hz starting) |
| CHX-2600KVA/130KV,260KV | 130KV,260KV | 20A@130KV | 2600KVA |
For U0=64KV cable For 72.5KV class GIS |
| 10A@260KV |
For U0=127KV cable For 145KV class GIS |
|||
| CHX-9000KVA/150KV,300KV | 150KV,300KV | 60A@150KV | 9000KVA |
For U0=87KV cable For 72.5KV class GIS |
| 30A@300KV |
For U0=160KV cable For 170KV class GIS |
|||
| CHX-10000KVA/250KV,500KV | 250KV,500KV | 40A@250KV | 10000KVA |
For U0=127KV cable For 145KV class GIS |
| 20A@500KV |
For U0=290KV cable For 362KV class GIS |
|||
| CHX-20000KVA/250KV,500KV | 250KV,500KV | 80A@250KV | 20000KVA |
For U0=127KV cable For 145KV class GIS |
| 40A@500KV |
For U0=290KV cable For 362KV class GIS |
|||
| CHX-21000KVA/350KV,700KV | 350KV,700KV | 60A@350KV | 21000KVA |
For U0=190KV cable For 170KV class GIS |
| 30A@700KV |
For U0=290KV cable For 550KV class GIS |
|||
| Special requirement can be made by order | ||||
VI. On-site test standard table from IEC 60840:2011 and IEC 62067:2011 for XLPE cable
VII. On-site insulation test standard table from IEC 62271-203:2011 for HV GIS