ISO14001 Standard Clean Room Air Conditioning System Air Handler
| Model SL-ZKW-()CW | 300 | 350 | 400 | 450 | 500 | 550 | 600 | 700 | 800 | 1000 | ||
| Air volume(m³/h) | 30000 | 35000 | 40000 | 45000 | 50000 | 55000 | 60000 | 70000 | 80000 | 100000 | ||
| Outlet air pressure(pa) | 600 | 600 | 600 | 600 | 600 | 800 | 800 | 800 | 800 | 800 | ||
| Supply fan capacity(kw) | 18.5 | 18.5 | 22 | 22 | 30 | 30 | 37 | 37 | 45 | 55 | ||
| Heating capacity(kw) | 72 | 84 | 96 | 96 | 1201 | 120 | 150 | 180 | 180 | 210 | ||
| Heating capacity(kg/h) | 21 | 30 | 30 | 45 | 45 | 60 | 72 | 90 | 100 | 120 | ||
| Filter type | Pre-filter G4 (Med-filter F8 / Nano carbon filtration) | |||||||||||
| Power | 3N-380V-50Hz | |||||||||||
| Cooling | 4 Rows Return Air | Return air(kw) | 179 | 210 | 245 | 277 | 306 | 340 | 375 | 440 | 504 | 590 |
| water flow(m³/h) | 28.2 | 36.2 | 42.1 | 47.6 | 53 | 58.2 | 64.6 | 76.1 | 86.8 | 101.3 | ||
| water resistance(m³/h) | 50 | 20 | 27 | 29 | 32 | 35 | 40 | 25 | 35 | 48 | ||
| pipe diameter (DN) | 80 | 65*2 | 65*2 | 80*2 | 80*2 | 80*2 | 80*2 | 100*2 | 100*2 | 100*2 | ||
| 4 Rows Fresh Air | All fresh air(kw) | 310 | 360 | 410 | 456 | 510 | 570 | 600 | 720 | 840 | 1020 | |
| water flow(m³/h) | 55 | 62.5 | 72.2 | 78.4 | 87.6 | 98 | 103.1 | 123.7 | 144.3 | 175.3 | ||
| water resistance(m³/h) | 35 | 40 | 31 | 38 | 43 | 48 | 36 | 48 | 35 | 50 | ||
| pipe diameter (DN) | 80*2 | 80*2 | 100*2 | 100*2 | 100*2 | 100*2 | 80*3 | 80*3 | 100*3 | 100*3 | ||
| 6 Rows Return Air | Return air(kw) | 210 | 240 | 280 | 310 | 350 | 380 | 400 | 490 | 560 | 680 | |
| water flow(m³/h) | 36 | 42.5 | 48.1 | 52.3 | 60 | 66 | 68.8 | 84.2 | 96.6 | 116.8 | ||
| water resistance(m³/h) | 25 | 0.3 | 35 | 40 | 49 | 26 | 34 | 39 | 32 | 40 | ||
| pipe diameter (DN) | 100 | 65*5 | 80*2 | 80*2 | 80*2 | 100*2 | 100*2 | 100*2 | 80*3 | 80*3 | ||
| 6 Rows Fresh Air | All fresh air(kw) | 420 | 456 | 532 | 590 | 665 | 720 | 760 | 930 | 1060 | 1290 | |
| water flow(m³/h) | 72.5 | 78.4 | 91.4 | 101 | 114.3 | 123.7 | 130 | 160 | 182 | 221.6 | ||
| water resistance(m³/h) | 40 | 45 | 50 | 38 | 42 | 48 | 31 | 40 | 50 | 45 | ||
| pipe diameter (DN) | 100*2 | 100*2 | 100*2 | 80*3 | 80*3 | 80*3 | 100*3 | 100*3 | 100*3 | 125*3 | ||
| 8 Rows Return Air | Return air(kw) | 264 | 290 | 330 | 380 | 420 | 470 | 480 | 590 | 680 | 820 | |
| water flow(m³/h) | 44.2 | 49.8 | 56.7 | 65.3 | 72.7 | 80.8 | 82.5 | 101.4 | 116.8 | 141 | ||
| water resistance(m³/h) | 29 | 35 | 40 | 31 | 36 | 42 | 45 | 30 | 40 | 42 | ||
| pipe diameter (DN) | 80*2 | 80*2 | 80*2 | 100*2 | 100*2 | 80*2 | 80*2 | 80*2 | 80*2 | 100*3 | ||
| 8 Rows Fresh Air | All fresh air(kw) | 500 | 550 | 630 | 720 | 800 | 890 | 910 | 1120 | 1290 | 1560 | |
| water flow(m³/h) | 85 | 94.5 | 108.3 | 123.7 | 137.5 | 153 | 1564 | 192.5 | 221.7 | 268 | ||
| water resistance(m³/h) | 40 | 38 | 46 | 50 | 38 | 45 | 35 | 40 | 45 | 42 | ||
| pipe diameter (DN) | 100*2 | 80*3 | 80*3 | 80*3 | 100*3 | 100*3 | 100*3 | 125*3 | 125*3 | 100*4 | ||
| Heating | 2 Rows Return Air | Return air(kw) | 170 | 199 | 235 | 260 | 290 | 32 | 350 | 408 | 467 | 565 |
| water flow(m³/h) | 15 | 17 | 20 | 23 | 25 | 27.5 | 30 | 35 | 40 | 49 | ||
| water resistance(m³/h) | 11.5 | 16 | 14 | 21 | 22 | 15 | 20 | 26 | 32 | 24 | ||
| pipe diameter (DN) | 65 | 65 | 80 | 80 | 80 | 100 | 100 | 100 | ||||
| 2 Rows Fresh Air | All fresh air(kw) | 256 | 298 | 349 | 392 | 426 | 468 | 500 | 598 | 685 | 793 | |
| water flow(m³/h) | 22 | 25 | 30 | 34 | 37 | 10.3 | 43 | 52 | 59 | 49 | ||
| water resistance(m³/h) | 20 | 24 | 25 | 14.5 | 14.9 | 19 | 22 | 17.8 | 15 | 16 | ||
| pipe diameter (DN) | 80 | 80 | 100 | 100 | 100 | 125 | 180 | 210 | 100*2 | |||
| 4 Rows Return Air | Return air(kw) | 270 | 316 | 370 | 415 | 4.5 | 5.5 | 7.8 | 10 | 739 | 855 | |
| water flow(m³/h) | 23.5 | 27.5 | 32 | 36 | 40 | 40 | 50 | 50 | 64.6 | 76.1 | ||
| water resistance(m³/h) | 16 | 13 | 12 | 110 | 140 | 200 | 250 | 320 | 10.5 | 20 | ||
| pipe diameter (DN) | 80 | 80 | 100 | 4.8 | 6.3 | 9 | 11 | 13.5 | 18.2 | |||
| 4 Rows Fresh Air | All fresh air(kw) | 400 | 470 | 548 | 616 | 670 | 750 | 822 | 972 | 1095 | 1340 | |
| water flow(m³/h) | 35 | 40 | 47 | 53 | 58 | 64.6 | 71 | 84 | 94 | 115 | ||
| water resistance(m³/h) | 20 | 17 | 24 | 27 | 27 | 29 | 31 | 35 | 42 | 25 | ||
| pipe diameter (DN) | 100 | 56 | 80 | 110 | 140 | 200 | 250 | 320 | 380 | |||
| Section size |
Standard | Length(mm) | 1960 | 2270 | 2270 | 2580 | 2580 | 3270 | 3270 | 3270 | 3270 | 3825 |
| height(mm) | 2040 | 2340 | 2340 | 2650 | 2650 | 2650 | 265 | 3340 | 3340 | 3340 | ||
| Function section |
Mixing section | Length(mm) | 800 | 1000 | 1000 | 1000 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 |
| Pre-filter section | Length(mm) | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | |
| Med-filter section | Length(mm) | 500 | 500 | 500 | 500 | 500 | 500 | 500 | 500 | 500 | 500 | |
| Cooling coil section | Length(mm) | 1000 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | |
| Heating section | Length(mm) | 100 | 500 | 500 | 500 | 500 | 600 | 600 | 600 | 600 | 600 | |
| Humidifying section | Length(mm) | 600 | 600 | 600 | 600 | 600 | 600 | 600 | 600 | 600 | 600 | |
| Fan section | Length(mm) | 1850 | 2000 | 2000 | 2000 | 2000 | 2200 | 2200 | 2300 | 2700 | 2700 | |
| Current balance section | Length(mm) | 700 | 800 | 500 | 800 | 800 | 800 | 800 | 800 | 800 | 800 | |
| Sound deadening section | Length(mm) | 1000 | 1200 | 1200 | 1200 | 1200 | 1200 | 1400 | 1400 | 1400 | 1400 | |
| Sterilization section | Length(mm) | 600 | 600 | 600 | 600 | 800 | 800 | 800 | 800 | 800 | 800 | |
| Air outlet section | Length(mm) | 800 | 1000 | 100 | 100 | 1200 | 1200 | 1500 | 1500 | 1500 | 1500 | |
indoor dry bulb/ wet bulb temp35/28℃, fresh air dry bulb/ wet bulb temp35/28℃
2. Heating condition conditions: supply and return water temp60/50℃,
indoor dry bulb/ wet bulb temp20/ -℃, fresh air dry bulb/ wet bulb temp7/6℃
3. The air volume, residual pressure and power in the table are standard parameters,
and are able to be customized
4. Heater, humidifier and heat recovery device are optional, which can be configured as spacific form according to customer's requirements
5. G4 filter is adopted as the unit standard, which can be configured as other form according to customer's requirements
6. The length and size are determined by the functional sections. Please consult us for details.
Application:
The units are widely used in the air system of many inductries like mechanical ,electronic, textile,medical,chemical,energy and foo inductries ,etc. the units are also ideal solution for restaurants, office buildings,hospitals,theaters,supermarkets and palaestra.