220VAC BLDC Electric Coolant Pump 120L/min Flow 23m Head for Industrial Chillers
Price:
Negotiable
MOQ:
1
Delivery Time:
Negotiable
Brand:
Bextremeshell
Product Description
Product Overview
High-efficiency BLDC electric coolant pump designed for industrial chiller systems, featuring advanced performance characteristics and robust construction.
Key Specifications
| Parameter | Value |
|---|---|
| Model | OWPA650B-1 |
| Rated Voltage | 220VAC |
| Operating Voltage Range | 170-275VAC |
| Rated Performance | 120L/min @ 180Kpa |
| Maximum Flow Rate | 180±5% L/min |
| Maximum Head | 23±1 m |
| Input Power | 700W±5% |
| Current Rating | 3.5±5% A |
| Service Life | 40,000 hours |
| IP Rating | IP67 |
| Noise Level | ≤65dB(A) |
| Weight | 4.4Kg |
Technical Features
- Stainless steel construction with natural finish
- Separated bracket design for flexible installation
- Speed range: 2500-5500rpm
- 3 pole pairs configuration
- Insulation rating: Class F
- Electrical strength: <1mA >500MΩ
- Flame retardant: Meets GB/T 2408 HB horizontal and V-0 vertical standards
- Mechanical strength: Complies with QC/T413-2015 engine severity rating
- Substance compliance: Meets GBT 30512-2014 requirements
Operating Conditions
Environmental Parameters
- Ambient temperature: -40°C to 85°C
- Liquid temperature: -40°C to 85°C
- Liquid compatibility: Commercial coolants with water/antifreeze ratios of 50/50 to 40/60
Installation Requirements
- Cooling system must be completely drained to vacuum before filling
- Consider vibration and noise requirements when selecting installation location
- Avoid positions where water can accumulate on connection surfaces
Typical Applications
- Energy storage thermal management systems
- Liquid-cooled charging cabinets
- Data center cooling systems
Electrical Specifications
| Parameter | Value |
|---|---|
| Resistance | 2.6±3%Ω |
| Inductance (Axis-Q) | 14mH |
| Inductance (Axis-D) | 13mH |
| BEMF | 24.5±3%V |
| Harness Length | 300mm (U V W Power cord) |
| Plug-in Connector | Amphenol AT04-3P-RD01-NFK |
Controller Compatibility
This pump requires a compatible inverter controller for operation. You can use our matching controller or select third-party controllers that meet the required protection functions to ensure normal pump operation.
Technical Documentation
Related Videos
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.
Company
Changzhou Bextreme Shell Motor Technology Co.,Ltd
Location
No.8 Tianshan road, Xinbei district,Changzhou,Jiangsu,China.
Contact Person
Sharon Xiao