The MIC200-UV/IR3 Flame Detector provides reliable fire detection for hydrogen and hydrocarbon-based flames with maximum 50-meter detection range and 120° field of view. Engineered for hazardous area applications with ExdⅡCT6 explosion-proof certification.
Technical Specifications
Parameter Specification
Detection Range 15-50 meters (depending on fuel source)
Response Time 5-10 seconds
Field of View IR: 90°, UV: 120°
Spectral Range IR: 4-5μm, UV: 260nm
Operating Voltage DC 24V
Operating Current ≤30mA normal, ≤45mA alarm
Temperature Range -10°C to +55°C
Explosion-Proof Rating ExdⅡCT6/DIP A20 TA,T6
Protection Rating IP66
Dimensions 19×16×11 cm
Weight 1.7 kg
Signal Output 4-20mA, RS485-RTU, Relay
MIC200-UV/IR3 Flame Detector unit showing rugged aluminum housing and mounting bracket
Key Features & Benefits
  • Dual UV/IR detection technology for enhanced false alarm immunity
  • 120° wide field of view for comprehensive coverage
  • Continuous Optical Path Monitoring (COPM) for reliability assurance
  • Window heater prevents condensation and icing in harsh environments
  • Multiple output options: 4-20mA, RS485, Modbus, relays
  • Data/event logger records alarms and faults in non-volatile memory
  • Rugged aluminum alloy housing with corrosion-resistant coating
  • Self-test functionality for window cleanliness and overall operation
  • Tilt mounting bracket for flexible installation above or below detector
Detection Technology
The MIC200-UV/IR3 combines ultraviolet and infrared sensors to monitor for hydrogen and hydrocarbon-based flames. This dual-spectrum approach significantly reduces false alarms while maintaining high detection sensitivity across various fuel sources including heptane, methane, propane, and butane.
Technical diagram showing UV/IR flame detection principle and sensor configuration
Industrial Applications
• Oil & Gas Facilities
• Chemical Storage Tanks
• Power Stations
• Refineries
• Loading/Unloading Facilities
• Tank Farms & Storage Areas
• Pump Rows & Manifolds
• Aircraft Hangars
• Hazardous Waste Treatment
Flame detector installation in industrial setting showing proper mounting and wiring
Certifications & Standards
Compliant with GB15631-2008 and GB3836-2000 series standards. ATEX and CE certified for use in hazardous locations including Zone 1 and Zone 2 areas.

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Beijing HiYi Technology Co., Ltd
Location Room 1302,Yufei Building, 42 Dongzhimenwai Street, Dongcheng District, Postcode:100027 Beijing,China
Contact Person Lisa Niu

Request A Quote

Please check your email address.
Your message must be at least 20 characters.