ADL3000-E Three Phase DIN Rail Energy Meter

Price Negotiable
Price: Negotiable
MOQ: 1 Pieces
Delivery Time: 2-3 days
Brand: Acrel
Product Description

General


This multifunction power meter is featured by small size, high accuracy and easy installation. It has functions including all electrical quantities measurement, electric energy calculation and management, single channel residual current measurement, and total harmonics (within 21 times) measurement. Remote communication and remote control functions can be realized due to the design of digital input and relay output. This energy meter is equipped with RS485 communication interface and configurable with Modbus RTU protocol, it is widely applied in a variety of control systems, SCADA systems and energy management systems.

 

Technical parameter


Specification

3 phase 3 wires, 3 phase 4 wires
Voltage

Reference voltage

3×100V, 3×380V,3×57.7/100V, 3×220/380V
Consumption

<10VA(Single phase)

Impedance

>2MΩ

Accuracy class Error±0.2%
Current Input current

3×1(6)A (second connection with 3- phase load line via extra selected CTs)

3×10(80)A (direct connection with 3-phase load line via CTs built in ADL3000-E)

Consumption

<1VA(Single phase rated current)

Accuracy class Error±0.2%
Power Active, reactive, apparent power, error±0.5℅
Frequency

45~65Hz, Error±0.2%

Temperature -40℃~99℃
Energy Active energy(Accuracy class:0.5, 1), reactive energy(Accuracy class 2)
Clock

≤0.5s/d

Energy pulse output 1 active optocoupler output, 1 reactive optocoupler output
Switching output

1 Switching output

Switching input 1 optocoupler input
Width of pulse 80±20ms
Pulse constant

6400imp/kWh,400imp/kWh(Correspond with the basic current)

Interface and communication

RS485:Modbus RTU

Range of communication address Modbus RTU:1~ 247;
Baud rate 1200bps~19200bps
Relative temperature -25℃~+55℃
Relative humidity ≤95℅(No condensation)

Features


 

Multi-rate/Flexible Tariff

● 4 Time zone

● 4 Tariff rate (Spike, Peak, Flat, Valley)

● 2 Time period list

● 14 Time period by day

● Data Frozen (last 48 months or last 90 days)

● Max demand and occurrence time

 

2 Channel RS485 Communication

● Protocol: MODBUS-RTU

● 1 channel RS485 or 2 channel RS485 both optional

 

DO/DI Switch

● 1 channel DO

● 1 channel DI

 

Wiring


Installation


Network


Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Jiangsu Acrel Electrical Manufacturing Co., LTD.
Location No. 9 Xincheng Road,Chengjiang Street, Jiangyin City, Jiangsu Province,China
Contact Person Dina Huang

Request A Quote

Please check your email address.
Your message must be at least 20 characters.