68mm Electric Power Tester Small Clamp Meter With Data Hold CT Technology
68mm Electric Power Tester Small Clamp Meter With Data Hold CT Technology
Introduction
VICTOR6800 Digital Clamp Leakage AC Current Meter With RS232 Peak And Data Hold CT Technology Small Size
Description
High Accuracy Clamp Leakage Current Meter is specially designed and manufactured for measuring AC leakage current. The meter adopts CT technology and digital integration technology, with the characteristics of small size, high precision and fully functional. It is widely used in electric power, communication, meteorology, railway, oil field, construction, metrology, scientific research and teaching units, industrial and mining enterprises, automobile circuit maintenance and other fields. Its sensing iron core is made of special alloy, adopts multi-layer shielding technology, and has strong anti-interference ability, which ensures the high precision, high stability and high reliability in the measurement of all year round without interruption.
The instrument is equipped with RS232 interface, communication cable and monitoring software. It can real time monitoring and query history online via the computer, and display dynamically, has the maximum, the minimum and the average value indication, with the alarm value setting and the alarm indication function, has the historical data reading, saves, prints and other functions. The meter also has peak hold, data hold and data storage and other functions, convenient to use, which is an essential tool for electrical safety inspection.
Technical Data
| VICTOR 6800 | |
| Range | 0.00mA~1200A |
| Resolution | 0.01mA |
| Accuracy(23℃±3℃, below 70%RH) | 0.00mA~59.9A: ±1.5%±5dgt |
| 60.00A~199A: ±2%±5dgt | |
| 200.0A~599A: ±3%±5dgt | |
| 600A~1200A: ±4%±5dgt | |
| Power | Zn-Mn dry battery,6F22,9V |
| Size of jaw | Φ68mm |
| Sampling Rate | about 2 times/s |
| USB Interface | Data stored in the memory of the meter via USB upload to PC, or on-line monitoring |
| Storage | 99units,all used when display FULL |
| Peak Hold | Push HOLD without release, the meter will show the peak value during the pushing period |
| Reading Hold | DH indicating when the reading is hold |
| Out of Range | OL indicating when the current is out of range |
| Working Current | 5mA |
| Line Voltage | circuit test below AC1600V |
| Range Shift | Automatically |
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.