6410A 6410B Digital Earth Resistance Clamp Meter Leakage Current Measurement
6410A 6410B Digital Earth Resistance Clamp Meter Leakage Current Measurement
VICTOR 6410 6410A 6410B Digital Clamp Earth Grounding Resistance Tester Leakage Current Measurement 0-30A Current 4 Digits LCD Display
Introduction
6410 series of Clamp Grounding Resistance Tester is a major breakthrough in traditional grounding resistance measurement. It is widely used in the grounding resistance measurement of the power, telecommunications, meteorology, oilfield, construction and the industrial and electrical equipment.
6410 series of Clamp Grounding Resistance Tester, in the measurement of a grounding system with loop, does not require breaking down the grounding down lead, and no need the auxiliary electrode. It is safe, fast and simple in use.
6410 series clamp grounding resistance meter can measure ground faults which cannot be measured by traditional methods. It can be used in applications where traditional methods cannot be measured, because the 6410series clamp grounding resistance meter measures the combined value of grounding body resistance and grounding lead resistance. .
In addition, the C type Clamp Grounding Resistance Tester is also able to measure the leakage current and the neutral current in the grounding system.
Technical Specifications
Power Source: 6VDC (4pcs 5# alkaline battery)
Working Temperature: -10 ° -55 ° C
Relative Humidity: 10%-90%
LCD: 4-digital LCD, 47mm (L) × 28.5mm (W)
Meter Size: 275mm (L); 85mm (W); 56mm (H)
Meter Weight (including batteries): 1130g
Protection Level: Double insulation
Structural Feature: Clamp and jaw type
Range Shift: Automatic
External Magnetic Field: <40A/m
External Electric Field: <1V/m
Single Measuring Time: 1 second
Measurement Resistance Frequency: >1KHz
Maximum Resistance Measurement Resolution: 0.001 Ω
Resistance Measurement Range: 0.01-1000 Ω
Current Measuring Range: 0.00-30.0A(C type)*
Measured Current Frequency: 50/65Hz
Storable Measurement Data: 99 Units
Setting Range of Resistance Alarm Critical Value: 1-199 Ω
Setting Range of Current Alarm Critical Value:1-499mA(C type)*
Note: with "*" item is limited to C type
Technical Data
| Model | Jaw Size (mm) | Range of Resistance (Ω) | Range of Current (A) | Storage Function | Alarm Function |
| 6410 | 55×32 | 0.01--1000 | -- | 99 Units | Yes |
| 6410A | 55×32 | 0.01--200 | -- | 99 Units | Yes |
| 6410B | 55×32 | 0.01--1000 | 0.0--.30.0 | 99 Units | Yes |
| Mode | Range | Resolution | Accuracy |
| Resistance Range | 0.010Ω-0.099Ω | 0.001Ω | ±(1%+0.01Ω) |
| 0.10Ω-0.99Ω | 0.01Ω | ±(1%+0.01Ω) | |
| 1.0Ω-49.9Ω | 0.1Ω | ±(1%+0.1Ω) | |
| 50.0Ω-99.5Ω | 0.5Ω | ±(2%+0.5Ω) | |
| 100Ω-199Ω | 1Ω | ±(3%+1Ω) | |
| 200Ω-395Ω | 5Ω | ±(6%+5Ω) | |
| 400-590Ω | 10Ω | ±(10%+10Ω) | |
| 600Ω-1000Ω | 20Ω | ±(20%+20Ω) | |
| Current Range | 0.00mA-9.95mA | 0.05mA | ±(2.5%+1mA) |
| 10.0mA-99.0mA | 0.1mA | ±(2.5%+5mA) | |
| 100mA -299mA | 1mA | ±(2.5%+10mA) | |
| 0.30A-2.99A | 0.01A | ±(2.5%+0.1A) | |
| 3.0A-9.9A | 0.1 A | ±(2.5%+0.3A) | |
| 10.0A-19.9A | 0.1 A | ±(2.5%+0.5A) | |
| 20.0A-30.0A | 0.1 A | ±(3%+1A) |