New and original FLUKE 1625-2 GEO Earth Ground Tester, in stock now
Price:
USD$2615
MOQ:
2
Delivery Time:
in stock
Brand:
FLUKE
Product Description
General Specifications
Memory Internal memory storage up to 1500 records accessible via USB port
Measuring function Interference voltage and frequency, earthing resistance 3- and 4-pole with/without clip-on current transformer, resistance 2-pole with AC, 2- and 4-pole with DC
Display 4 digit (2999 Digit) - 7 segment liquid crystal display, with improved visibility
Operation Central rotary switch and function keys
Temperature Range
Operating temperature -10°C to 50°C (14°F to 122°F)
Storage temperature -30°C to 60°C (-22°F to 140°F)
Temperature coefficient ±0.1% of reading/°C < 18°C > 28°C
Type of protection IP56 for case, IP40 for battery door according to EN60529
Max voltage Warning – socket "clamp" to socket E, ES, S or H
Urms = 0 V
Sockets E, ES, S or H to each other in any combination, max. Urms = 250 V (pertains to misuse)
Safety Protection by double and/or reinforced insulation. Max. 50 V to earth per IEC61010-1. Pollution degree 2
Quality standard Developed, designed and manufactured to comply with DIN ISO 9001
External field influence Complies with DIN 43780 (8/76)
Auxiliary power 6 x 1.5 V alkaline (IEC LR6 or type AA)
Battery life span With IEC LR6/type AA: typ. 3,000 measurements (RE+RH ≤ 1 kΩ)
With IEC LR6/type AA: typ. 6,000 measurements (RE + RH > 10 kΩ)
Dimensions (W x H x D) 250 x 133 x 187 mm (9.75 x 5.25 x 7.35 in)
Weight ≤ 1.1 kg (2.43 lb) without accessories 7.6 kg (16.8 lb) incl. accessories and batteries in carrying case
Case material Polyester
Measurement of Interference Voltage DC + AC (UST)
Measuring limits of error: method Full wave rectification
Measuring range 1 V to 50 V
Display range 0.0 V to 50 V
Resolution 0.1 V
Frequency range DC/AC 45 Hz to 400 Hz sine
Accuracy ±(5% of rdg + 5 digit)
Measuring sequence Approx. 4 measurements/s
Internal resistance Approx. 1.5 MΩ
Max. overload Urms = 250 V
Measurement of Interference Frequency (F)
Measuring limits of error: method Measurement of oscillation period of the interference voltage
Measuring range 6.0 Hz to 400 Hz
Display range 16.0 Hz to 299.9 Hz to 999 Hz
Resolution 0.1 Hz to 1 Hz
Range 1 V to 50 V
Accuracy ±(1% of rdg + 2 digit)