Flowserve Logix 3200MD Digital Valve Positioner - 4-20 mA Input, HART Protocol, Auto-Tuning with Dynamic Gain Selection

Price Negotiable
Price: usd2900 piece/pieces
MOQ: 1
Delivery Time: 5-10 Work days
Brand: Flowserve
Product Description
Product Overview
The Flowserve Logix 3200MD digital positioner is a two-wire 4-20 mA input digital valve positioner designed for precise control of industrial valves. This advanced instrument features auto-tuning with dynamic gain selection and supports HART protocol communications for remote configuration and monitoring.
Key Features & Benefits
  • Local status LED indicators for real-time monitoring
  • Local DIP switches and calibration buttons for easy setup
  • Auto-tuning with dynamic gain selection for optimal performance
  • HART 5 protocol support for two-way remote communications
  • Simple calibration via local user interface
Safety Certifications
  • Explosion proof enclosure rated Class I Division 1 Groups B-D, Ex d IIB+H2, AEx d IIB+H2
  • Intrinsically Safe Rated Class I, Div 1, Groups A-G, Ex ia IIC, AEx ia IIC
  • Non-Incendive Class I Div 2 A-D, Ex nA
  • SIL 2 safety integrity level certification
Technical Specifications
Parameter Specification
Brand Name Flowserve
Model 3200Md-10-d6-e-04-40-0g-0f
Power Supply Two-wire, 4-20 mA 10.0 to 30.0 VDC
Compliance Voltage 10.0 VDC @ 20 mA
Communications HART Protocol
Temperature Range -40° to 176°F (-40° to 80°C)
Product Images
Flowserve Logix 3200MD Digital Positioner front view Flowserve Logix 3200MD Digital Positioner side view Flowserve Logix 3200MD Digital Positioner installation view Flowserve Logix 3200MD Digital Positioner technical diagram
Operation & Configuration
The Logix 3200MD positioner is an electric feedback instrument that can control both double- and single-acting actuators with linear or rotary mountings. The positioner receives power from the two-wire 4-20 mA input signal and supports two command signal sources: Analog (4-20 mA signal) and Digital (HART protocol).
Control Function
In Analog source mode, the 4-20 mA signal is converted to a percentage, with 0% representing valve closed position and 100% representing valve open position. The command source can be configured using ValveSight software, HART 375 communicator, or other host software.
Important Note: The air supply must conform to ISA Standard ISA 7.0.01 (dew point at least 18°F below ambient temperature, particle size below five microns—one micron recommended—and oil content not to exceed one part per million).