384V/50Amp High Voltage BMS with 2U Standard Case and Master-Slave Structure for Battery Management
384V 50Amp high voltage battery management system featuring a 2U standard 19-inch case design. Engineered for efficiency, stability, and reliability with dimensions: W482×H89×D500mm.
Supports multiple communication protocols including RS485, CAN, LAN, and dry contact interfaces.
Features 8 temperature sensors, fan voltage 48V (17S-24S 12V), voltage detection range 0-5V, 12V power supply with consumption less than 20mA, and CAN2.0 B communication.
18 Pin+20Pin wire with standard lengths of 600mm, 900mm, and 1200mm. Temperature sensor wire available in 600mm, 900mm, and 1200mm lengths. Fan wire: 600mm standard length.
Communication wire connects from master BMS to each BMU with cascade connection, with the last port designated for terminal resistance.
| No. | Name | Explain | Matters Needing Attention |
|---|---|---|---|
| 1 | B+ B- | Power port connected to battery side total positive and total negative | Plug-in terminal (GPS50AFP) |
| 2 | P+ P- | Power port connected to charging equipment (UPS) or DC bus | Plug-in terminal (GPS50AFP) |
| 3 | AC 220V | The municipal power supply signal input port must be taken from the UPS output side | When there is mains power, the BMS is turned on; when there is no mains power, the BMS is turned off (ensure that the BMS and the mains are turned on and off synchronously to save the self-consumption of the battery by the BMS) |
| 4 | ON OFF | On: the circuit breaker is on; Off: the circuit breaker is disconnected | When the handle of the circuit breaker is in the tripping state in the middle position, it needs to be turned to Off before it can be closed. |
| 5 | D1 D1 D2 D2 | Two dry contact output reserved | Prohibit charging, Prohibit charging Dry contact output |
| 6 | Start | DC start button: start RBMS system by taking power from the battery side. | The system is connected to the battery. After the circuit breaker is closed, press and wait for the light to light up, indicating that the system is powered on. |
| 7 | System | System status indicator | System normal: the green light is always on System alarm: the yellow light is always on Self test failure and protection status: the red light is always on Charging: the green light flashes Discharge: red light flashing Self checking: red and green flashing alternately Pre-charging: yellow flashing |
| 8 | 1 2 4 8 | ID allocation: when multiple RBMs are used in parallel, the ID is allocated by setting the dial switch. You must start with 1 | The dial switch has 4 bits in total and supports up to 15 RBMs Parallel machine 1 ON: ID+1 2 ON: ID+2 3 ON: ID+4 4 ON: ID+8 |
| 9 | LAN | RBMS host computer system software can be connected to PC through network cable | The network cable standard is CAT5 or above, and can be connected by cross line or straight line. The line sequence can be according to the standard tia-586A or tia-568B |
| 10 | T-CAN T-485 | Terminal matching resistance setting during can and 485 communication Setting Description: (120R), on is valid | For parallel application, only the last one needs to be set; Single machine should be used flexibly according to the site conditions (interference, communication distance, etc.) |
| 11 | COM1 COM2 | RBMs external communication port: In parallel application: communicate with SBMS In stand-alone application: communicate with UPS / PCS external equipment | The shielded twisted-pair cable harness must be used randomly. The cable sequence is defined in the cable harness label |
| 12 | GND 24V | For supplying power to SBMS | |
| 13 | BMU-OUT | Communication interface with BMU | communication with BMU level |
| 14 | RBMS cabinet ground point | Must be grounded, and the grounding resistance is less than 1Ω |
- Advanced battery management system - The highly integrated battery management system can realize seamless monitoring.
- Perfect self-checking and running status checking function, with HMI display screen, system running information is clear at a glance.
- Complete and reliable system control and protection strategies, comprehensively guarantee battery safety, and escort to extend the life of battery packs.
- Modular design, configurable and expandable - multiple energy storage units can be flexibly combined and expanded into a larger energy storage system.
- Abundant communication interfaces - multiple RS485, CAN, Ethernet, dry contact input and output interfaces, supporting communication with most PCS and monitoring servers on the market.
- The communication interface protocol is flexible - the factory comes with the company's communication protocol, and it can also be adapted to the PCS of different manufacturers according to customer needs.
- The built-in large-capacity memory chip can store a large amount of key operating data, and an SD card can be added to realize battery historical data storage.
- Automatic circulation control and automatic parallel/offline control can easily realize the parallel connection of battery packs.
Hunan Group Control Energy Technology Co., Ltd. (GCE) is a high-tech company specializing in the research and development of BMS and lithium battery peripheral equipment. The high-performance intelligent lithium battery management system produced by our company adopts the international leading technology, which greatly improves the battery management efficiency and prolongs the service life of lithium battery. The advanced BMS control strategy avoids the difficulties and instability faced by most competitors for our BMS.