10 Ton Portable Industrial Chiller Units For Blowing Machine
10ton Industrial Chiller Units For Industrial Process Cooling Machince for Blowing Machine
The film blowing machine is currently the most common plastic bag production machine on the market. It heats and melts plastic particles and then blows them into films. There are many types of film blowing machines, including PE, POF, PVC, etc.
Specification
|
Model Item |
ACK-10(D) | |
| Nominal cooling capacity | Kcal/h | 24424 |
| kw | 28.4 | |
| Input power | kw | 11.22 |
| Power supply | 3PH/380V/50HZ | |
| Refrigerant | Type | R22 |
| Type of control | Expansion valve | |
| Compressor | Type | Hermetic scroll type |
| Power (kw) | 8.8 | |
| Condenser | Type |
Finned copper tube+low noise outer rotor fan |
| Fan | Power(kw) | 0.92 |
| Cooling air flow | 10000 | |
| Evaporator | Type | Shell and tube |
| Chilled water flow | 5 | |
| Tank volume(L) | 85 | |
| Inlet/outlet pipe chiller( inch) | 1-1/2 | |
| Water pump | Power(KW) | 1.5 |
| Lift(m) | 20 | |
| Safety protection | compressor over temperature, over-current protection, high and low pressure protection, over -temperature protection ,flow switch protection,phase sequence or missing phase protection,exhaust overheating protection | |
| Net weight | kg | 500 |
| Dimension | mm | 1530*780*1630 |
Anges chiller Application Range.
- Electroplating industry: Control plating temperature, increase the density and smoothness of the plated parts.
- Machinery industry: Control the pressure oil temperature of the oil pressure system.
- Construction industry: chilled water for concrete.
- Vacuum coating: Control the temperature of the vacuum coating machine.
- Food industry: Controlling the temperature of fermented foods.
- Pharmaceutical industry: Controlling the temperature control of fermented drugs.
THE AFTER-SALE SERVICE OF ANGES CHILLER!
- After finish the production, we will debug the production line, take photos, videos and send them to customers via mail or instant tools
- After the commissioning, we will package the equipment by standard export package for shipment.
- Engineers, sales managers and after-sales service manager will form a after-sales team, online and off line, to follow the customers' project.
FAQ
1.How does a chiller system work?
Chiller has two circulation,one is process water circulation,the other is refrigerant gas circulation.Heat picked up from the process.Heat transfers to refrigerant circulation.Heat is remove to air or water.
2.How to calculate cooling capacity for chillers?
Cooling Capacity(kw)= Flow Rate(m3/h)*Temp Change(T1-t2)/0.86
Heat Load= C(specific heat)* M(quality output per hour )*Temp Change(T1-T2)
3.How can we do for chiller maintenance ?
Step 1: Keep Tubes Clean
Step 2: Ensure a Leak-free Unit
Step 3: Sustain Proper Water Treatment(prevent scale, corrosion)
Step 4: Analyze Oil and Refrigerant
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.