50TR Air Cooled Industrial Chiller 140.9 kW Cooling Capacity 45.52 kW Power for Extrusion Machines

Price Negotiable
Price: negotiated
MOQ: 1
Delivery Time: 15 days
Brand: SZAGS
Product Description
50TR Customizable Air Cooled Chiller Technical Specifications
Specification Value
Model HBC-50(F)
Nominal Cooling Capacity 121,191 Kcal/h (140.9 kW)
Input Power 45.52 kW
Power Supply 3PH 220~480V 50/60HZ
Refrigerant Type R22/407C/410A/134A (Capillary Control)
Compressor Hermetic Scroll (38.4 kW)
Condenser Finned Copper Tube + Low Noise Outer Rotor Fan
Fan Power: 3.12 kW
Cooling Air Flow: 50,000 m³/h
Evaporator Shell and Tube
Chilled Fluid Flow: 24.3 m³/h
Volume: 620 L
Inlet/Outlet Pipe: 3"
Pump Power: 4 kW
Flow: 24.3 m³/h
Lift: 22 m
Safety Protection Compressor over temperature, over load, high/low pressure, flow switch, reversed/lacking phase, anti-freezing, fusible protection
Weight 1,450 kg
Dimensions 2350 × 1760 × 2100 mm
Benefits for Extrusion Machine Cooling
  • Rapid Cooling: Quickly cools extruded materials to ensure rapid solidification and precise shaping
  • Quality Maintenance: Controls cooling to ensure dimensional accuracy and shape stability, reducing deformations
  • Enhanced Efficiency: Enables continuous operation by eliminating extended cooling periods
  • Energy Savings: More efficient than traditional air cooling methods, reducing operating costs
  • Material Adaptability: Adjusts cooling effects for various extrusion materials and process requirements
Comprehensive After-Sales Service
  • Complete production line debugging with photo/video documentation
  • Standard export packaging for secure international shipment
  • Dedicated after-sales team including engineers and managers for ongoing project support
Frequently Asked Questions
How does a chiller system work?

Chillers operate with two circulation systems: process water circulation and refrigerant gas circulation. Heat is transferred from the process to the refrigerant and then dissipated to air or water.

How to calculate cooling capacity for chillers?

Cooling Capacity (kW) = Flow Rate (m³/h) × Temperature Change (T1-T2) ÷ 0.86

How can we perform chiller maintenance?
  • Step 1: Keep tubes clean
  • Step 2: Ensure leak-free operation
  • Step 3: Maintain proper water treatment to prevent scale and corrosion
  • Step 4: Regularly analyze oil and refrigerant quality

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Shenzhen Anges Machinery Co., Ltd
Location Room 1610,Xinlong Building,Baishilong Community,Minzhi Street,Longhua District,Shenzhen,China
Contact Person Sam Lee

Request A Quote

Please check your email address.
Your message must be at least 20 characters.