NET WEIGHT:8.1KG
MODEL: ZDMS0.6/10S-LZ II
SENSOR:IR SENSOR
VOLTAGE:220V
COMMUNICATION METHOD:CAN
KEYWORD:INTELLIGENT FIRE MONITOR
Smart firefighting robot automatic fire suppression system


|
No
|
Item
|
Standard &Requirements
|
Inspection results
|
|
|
|
1
|
Rated working pressure (MPa)
|
≤0.8
|
0.6
|
/
|
|
|
2
|
Rated flow (L / s)
|
5×(1±8%)
|
5.05
|
/
|
|
|
3
|
Maximum protection radius(m)
|
≥30
|
30
|
/
|
|
|
4
|
Jet radius (m)
|
≥34
|
34
|
/
|
|
|
5
|
Monitoring radius(m)
|
≥40
|
40
|
/
|
|
|
6
|
Positioning time(s)
|
≤30
|
29.5
|
29.9
|
|
|
7
|
Installation height (m)
|
6~15
|
6
|
15
|
|
|
8
|
Horizontal swing angle(°)
|
≥180
|
360
|
|
|
|
9
|
Minimum pitch profile(°)
|
-90~+30
|
-90~+30
|
|
|
|
10
|
Diameter of water-inlet(mm)
|
Φ 34.5 ± 0.5
|
Φ 34.5 ± 0.5
|
|
|
|
11
|
Diameter of water-outlet(mm)
|
Φ 15.5 ± 0.5
|
Φ 15.5 ± 0.5
|
|
|